FC Frico Control - Quick guide EN FC Control system The air curtain must be supplemented with a control system. FC Control system helps to create many smart and energy saving features. In addition to our four packages, components can be added to expand and customize the system.
FC Direct - FCDA FC Frico Control - Quick guide G 1 2 G 1 2 A1 A2 GND Sensor PC Board inside air curtain B1 B2 D1 D2 Com NO NC Sensor GND Sensor FCRTX FCOTX HI LO HI +12V GND E1 E2 Actuator 24V - + +12V L N PE RED GRY HI WTA BUS 2 BLK BUS 2 LO Control Panel BUS 1 LO GND +12V FCDC GND 230V~ BUS 1 LO SDM (VPFC/VMFC) HI +12V GND FCOTX FCRTX FCDC PC Board inside air curtain 230V~ Control Panel SDM (VPFC/VMFC) 3
FC Smart - Sensor FCRTX FCOTX FCSA FC Frico Control - Quick guide G 1 2 GND Sensor FCRTX FCOTX A1 A2 GND Sensor on n PC Board inside air curtain B1 B2 D1 D2 E1 E2 - WTA HI LO BUS 2 LO GND +12V HI GND +12V +12V BUS 1 HI BUS 2 BLK Control Panel LO + E1 E2 Actuator 24V - + Set up in 230V~ Setup Guide RED GRY BUS 1 Control Panel BLK LO 230V~ L N PE S GND HI L N PE RED GRY HI Actuator 24V WTA Com NO NC +12V PC Board inside air curtain LO GND BUS 2 HI BUS 1 L
FC Frico Control - Quick guide FC Pro - FCPA Sensor FCRTX FCOTX GND A1 A2 PC Board inside air curtain B1 B2 D1 D2 Com NO NC G 1 2 GND Sensor Config input* HI +12V GND LO Actuator 24V + L N PE RED GRY - BLK HI LO HI LO GND +12V +12V E1 E2 FCWTA BUS 2 WTA BUS 2 Control Panel LO 230V~ * SDM (VPFC/VMFC) Set up in Setup Guide HI +12V GND BUS 2 LO FCTXRF* FCLAP HI +12V GND LO BUS 1 BUS 1 BUS 1 GND FCDC HI +12V GND Sensor Config input* FCDC PC Board inside air curtain
FC Building - FCBA FC Frico Control - Quick guide G 1 2 G 1 2 A1 A2 GND Sensor PC Board inside air curtain B1 B2 D1 D2 Com NO NC Sensor GND Sensor FCRTX FCOTX Actuator 24V + HI +12V LO L N PE RED GRY - BLK HI LO HI E1 E2 Control Panel GND BUS 1 WTA BUS 2 FCWTA BUS 2 LO +12V GND BUS 1 LO GND +12V FCDC 230V~ SDM (VPFC/VMFC) HI +12V GND E1 E2 E1 E2 E1 E2 E1 E2 E1 E2 E1 E2 + Modbus RS485 INPUT OUTPUT FanSpd S.Temp R.
FC Frico Control - Quick guide Termination at PC Board HI LO HI BUS 2 LO GND +12V GND +12V HI BUS 1 LO HI BUS 2 LO GND +12V GND +12V HI LO HI BUS 1 BUS 2 LO GND +12V GND +12V BUS 1 To reduce the risk of interference, the communication BUS should be terminated at each end, i.e. in the units that are located at the start and at the end of the BUS respectively. On delivery, all buses are pre-connected with a 120 Ohm resistor between terminals HI and LO on BUS2.
EN FC Frico Control - Quick guide Start up 1. Check that all components and accessories are enclosed. 2. Assemble and connect system, consult wiring diagrams. 3. Power-up the system. 4. The system automatically identifies all components, even when they are added at a later stage. 5. Connecting a new product must always be made with the power off.
EN FC Frico Control - Quick guide Control panel Overview 8 7 6 1 Keypad 1 Increase 2 Decrease 3 Menu / OK / Confirm 4 Fan 5 Cancel / Back 4 and 5 appear after pressing twice on menu button.
EN FC Frico Control - Quick guide Fan speed when door is open Fan menu Press twice to activate keypad and hidden buttons. Press twice to activate keypad and hidden buttons. Press to set fan speed Press and hold for 2 seconds. Set the fan speed: 0-100-Auto / 0-3-Auto. Auto requires outdoor temperature information (FCOTX / FCTXRF / outdoor temperature signal in FCBAP). Home screen Browse between the menu options.
FC Frico Control - Quick guide EN Fan menu Menu options Functions Default settings Description FAnH Maximum fan speed in Auto mode. 100 or 3 (100% or step 3) Increase/decrease with up/down arrow. Confirm with OK. FAnL Minimum fan speed in Auto mode. 0 Increase/decrease with up/down arrow. Confirm with OK. FAnC Fan speed closed door. 25 or 1 Increase/decrease with up/down (25% or step arrow. Confirm with OK. Fan speed 1) if there is a need for heat when door is closed.
EN FC Frico Control - Quick guide User menu Press to activate keypad. Press and hold for 2 seconds. Home screen Browse between the menu options. Confirm or Exit without saving See the table on the following page for the possible choices.
FC Frico Control - Quick guide EN User menu Menu options Functions dAtE For week program. Default settings Description - Increase/decrease with up/down arrow. Confirm each step with OK. Set the following: - year - month - day - time (00:00) tHi For week program. Set the desired room temperature (set point temperature) for comfort mode. 21 °C Increase/decrease with up/down arrow. Confirm with OK. tLo For week program. Set the desired room temperature (set point temperature) for reduced mode.
EN FC Frico Control - Quick guide Week program The FC has nine preset weekly programs (P1P9) and one customized (P0). Customized program is possible via FC Smart and FC Pro through the mobile app.
FC Frico Control - Quick guide EN Settings Settings are changed in User Menu: Press to activate keypad. Press and hold for 2 seconds. Enter the number for the setting that will be changed using up/down arrows, confirm each digit with OK. See table. Browse to SEt. Select desired value according to table. Confirm Confirm Enter password using up/down arrows, confirm each digit with OK. Password: 1932.
EN FC Frico Control - Quick guide Settings - Outdoor temperature sensor, requires FCOTX / FCTXRF / outdoor signal from FCBAP # Functions Default settings Description 374 Outdoor temperature heat blocking 1 (enabled) 0 (disabled) / 1 (enabled) If enabled, the heat is blocked when temperature exceeds the set point #376. 376 Outdoor temperature heat blocking - set point 150 (15.0 °C) Set point for Outdoor temperature heat blocking in 0.1 °C. 663 Block water bypass due to outdoor temperature.
FC Frico Control - Quick guide EN Settings - Water heated air curtain # Functions 662 Bypass 1 (enabled) 0 (disabled) / 1 (enabled) Allows time controlled or temperature* controlled bleeding. *Requires return water temperature sensor and mobile app. 666 Bypass temperature set point - WTA 300 (30.0 °C) 0-50 °C 657 Return water temperature control 0 (disabled) 0 (disabled) / 1 (enabled) Controls the return water temperature. Requires return water temperature sensor and mobile app.
EN FC Frico Control - Quick guide Reset alarm To reset manually, press X for 2 seconds where the serial number for an alarm is displayed (see User Menu). The majority of the alarms reset automatically, once the problem is corrected. The last four digits of the serial number for the faulty product, can be found on the data label on the outside of each product.
FC Frico Control - Quick guide EN Troubleshooting Error code Cause Action A 19 Frost protection alarm Ensure that the heating is on and working. A 20 Frost protection alarm from return water temperature sensor. A 21 Contact lost with RF sensor, FCTXRF Check the batteries. If low, replace them. If the batteries are ok, check the local access point. A 23 RF sensor out of batteries. Replace the batteries. A 25 No water heat Check the water supply temperature and flow.
Tel: +46 31 336 86 00 mailbox@frico.se www.frico.net For latest updated information and information about your local contact: www.frico.