Quickguide Frico Control FCSA FCDA FCPA FCBA
#
374
376
150 (15.0 °C)
663
664
20 (2.0 °C)
578*
0 (%) 0-100 %
579*
75 (%) 0-100 %
580*
-50 (-5.0 °C)
581*
320 (32.0 °C)
582*
180 (18.0 °C)
583*
230 (23.0 °C)
Fan speed
(%)
Outdoor
temperature
(°C)
a - #580
b - #581
c - #582
d - #583
High - #579
Low - #578
EC fans admits stepless speed control.
AC fans will automatically re-calculate to steps.
a
b
c
d
FC Frico Control - Quick guide
16
EN
Settings - Outdoor temperature sensor, requires FCOTX / FCTXRF / outdoor signal from FCBAP
Functions Default settings Description
*See gure below.
AC fan speed will automatically be converted to steps.
Outdoor temperature
heat blocking
0 (disabled) / 1 (enabled)
If enabled, the heat is blocked when temperature
exceeds the set point #376.
1 (enabled)
Outdoor temperature
heat blocking - set point
Set point for Outdoor temperature heat blocking in
0.1 °C.
Block water bypass due
to outdoor temperature.
0 (disabled) / 1 (enabled)
If enabled, the water bypass is blocked when
temperature is above the set point #664.
1 (enabled)
Block water bypass due
to outdoor temperature -
set point.
Set point for Block water bypass due to outdoor
temperature.
Auto fan low
Low fan speed in auto fan mode.
Auto fan high
High fan speed in auto fan mode.
Auto fan set point - Cold
high
Set point for high fan speed in cold conditions.
Auto fan set point -
Warm high
Set point for high fan speed in warm conditions.
Auto fan set point - Cold
low
Set point for low fan speed in cold conditions.
Auto fan set point -
Warm low
Set point for low fan speed in warm conditions.
EC fans admit stepless control.
Outdoor temperature [°C]
Fan speed [%]