Quickguide Frico Control FCSA FCDA FCPA FCBA

#
662
666
300 (30.0 °C) 0-50 °C
657
658
370 (37.0 °C) 15-90 °C
545
546
180 (s) 0-1800 s
#
681
682
20 (%) -100 - 100
686
0
FC Frico Control - Quick guide
17
EN
Settings - Water heated air curtain
Settings - Vestibule, requires FC Smart or FC Pro and is set in mobile app
Functions Default settings Description
Functions Default settings Description
1 (enabled)
1 (enabled)
0 (disabled)
0 (disabled)
Bypass 0 (disabled) / 1 (enabled)
Allows time controlled or temperature* controlled
bleeding. *Requires return water temperature
sensor and mobile app.
Bypass temperature set
point - WTA
Return water
temperature control
0 (disabled) / 1 (enabled)
Controls the return water temperature. Requires
return water temperature sensor and mobile app.
Return water
temperature set point
Requires return water temperature sensor and
mobile app.
Actuator exercise 0 (disabled) / 1 (enabled)
The actuator is fully opened and closed for a set time
(#546) every Monday morning at 2AM.
Actuator exercise time
Time that the actuator rst is open and then is
closed.
Vestibule function
0 (disabled)
1 (inner air curtain)
2 (outer air curtain)
Identifying the placement of each air curtain. Must
be set up in mobile app.
Vestibule set up
Difference from the inner door.
0 (disabled) / 1 (enabled)
Activates a higher fan speed and a lower
temperature at the outer door and a lower fan
speed and higher temperature at the inner door.
Vestibule function - fan
adjustment in outer door