Quickguide Frico Control FCSA FCDA FCPA FCBA

FC Frico Control - Quick guide
19
EN
A 19
A 20
A 25
A 26
A 27
A 28
A 21 Contact lost with RF sensor, FCTXRF
A 23
Frost protection alarm
Frost protection alarm from return water
temperature sensor.
No water heat
No electrical heat
Filter alarm - timer
Filter alarm - pressure guard
Error code ActionCause
RF sensor out of batteries.
Check the batteries. If low, replace them. If the
batteries are ok, check the local access point.
Ensure that the heating is on and working.
Check the water supply temperature and
ow.
Check the electrical supply. Check the overheat
protection, see manual for the air curtain.
Clean the lter.
Reset the alarm manually.
Replace the batteries.
A 35
A 36
A 37
A 38
A 39
A 33
BMS communication error
BMS invalid data
Parameter error
Outlet sensor missing
Inlet sensor missing
Motor alarm
Check the BMS connection.
Contact Frico.
Check the sensor connections.
Determine which fan is not functioning and
replace it.
When error codes are displayed, the system continues to operate with
the components that are functioning. If all room temperature sensors,
including the temperature sensor in the control panel, have lost
contact, the system will run at 25% heat output.
If the problems continue, please contact Frico for support.
Troubleshooting