Quickguide Frico Control FCSA FCDA FCPA FCBA

FC Frico Control - Quick guide
7
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1 BUS 2
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1 BUS 2
GND
GND
HI
HI
LO
LO
+12V
+12V
BUS 1BUS 2
Termination at PC Board
To reduce the risk of interference, the communication BUS should be terminated at each end, i.e. in the units
that are located at the start and at the end of the BUS respectively. On delivery, all buses are pre-connected
with a 120 Ohm resistor between terminals HI and LO on BUS2. When making further connections, remove the
resistor. As an alternative to resistance, the termination switch on the board can be set to the "ON" position.
To reduce the risk of interference, the communication BUS should be terminated at each end, i.e. in
the units that are located at the start and at the end of the BUS respectively. On delivery, all buses are
pre-connected with a 120 Ohm resistor between terminals HI and LO on BUS2. When making further
connections, remove the resistor. As an alternative to resistance, the termination switch on the board
can be set to the "ON" position.