DATASHEET AES D2M

Connection diagram AES-D2M
www.systemair.de
KW
4
5,5
7,5
Fuse
T 35 A
T 50 A
T 63 A
T 20 A
T 25 A
T 35 A
* 5x 6 qmm
* 5x10 qmm
* 5x16 qmm
* 4x2,5 qmm
* 4x4 qmm
* 4x6 qmm
Fuse
F1, F3
Supply
-W1
Smoke extract fan
-W2, W3
*
All specifications, minimum cross-sections
without consideration of layout, cable
length and network type for cables in the
functional integrity design E90
or layout F90.
The connection of the auxiliary contacts
of F1 and the cables L01, unit 1, N
see data sheet AES-ST3.2
The current value of the motor protection
relay has to be set before placing in
operation.
A
Edition Version
04.16
Control
board
AES-ST3.2