AES VDMA 24177

1
Controllers for fans for keeping buildings free
of smoke and heat in case of fire
Excerpt from VDMA standard sheet VDMA 24177 Sept. 2003
Foreword
Fans for keeping buildings free of smoke and heat (hereinafter referred to as smoke
extraction fans) serve in case of fire to extract flue gases from the section affected by the fire
with the aim of maintaining a low-smoke layer beneath the smoke layer over a defined period
of time in order to enable persons to rescue themselves and to allow the fire brigade access
for fire extinguishing and rescue actions or to establish controlled pressure differences and
hence to prevent the escape of smoke into escape and rescue routes.
Motor control
Smoke extraction fans that are also used for daily ventilation can be manufactured so that
they are controllable in ventilation mode.
They are almost always controlled by means of frequency controllers or dual-speed motors
(Dahlander circuit or separate windings).
The motors may not be operated via frequency controllers or similar control devices in smoke
extraction mode due to the increased risk of failure; instead they must be connected directly
to the main distributor via the electricity network.
This does not apply if the function of the frequency controller/motor unit has been tested
according to the test standards EN 12103-3 or DIN 18232-6 and carries building authority
approval.
Modes of operation
Smoke extraction fans can be operated single-stage, i.e. with a single speed, or multi-stage,
which means dual-speed or Dahlander circuit; this makes needs-based ventilation possible
(e.g. dependent on the CO content in garages).
Further modes of operation, such as speed regulation by lowering the voltage with a
transformer or control using a frequency controller are permissible only if the motor
manufacture has expressly approved the motor for this.
In the event of fire it must be ensured in every case that the upstream speed controller is
bridged and that operation takes place at the rated speed.
Repair switch
In accordance with DIN EN 60204-1 (VDE 0113-1) a repair switch must be provided in direct
proximity to the fan for maintenance and repair work if the control cabinet is not visible from
the fan.
The repair switch is to be secured in the operating position against unauthorised operation.
(e.g. by a padlock or implementation as a key switch).
Control cabinet
The control cabinet is to be installed in a room separated from the smoke extraction area by
means of fire protection measures.
Requirements for maintaining the function of cabling systems and distributors
The maintenance of the power supply for the smoke extraction fans must be guaranteed in
the case of fire. The duration of maintenance of the function must correspond at least to the
time classification of the component to be supplied. The duration of maintenance of the
function of the cabling systems must be at least 90 minutes.

Summary of content (2 pages)