Installation, Operation and Maintenance instruction KBT Thermo box fan AC KBT Thermo box fan EC EN
Table of content 1 Introduction .......................................................... 1 1.1 Product description ...................................... 1 1.2 Intended use .............................................. 1 1.3 Document description................................... 1 1.4 Product overview......................................... 1 1.5 Name plate ................................................ 2 1.5.1 Type designation ............................. 2 1.6 Product liability...................
1 Introduction 1.2 Intended use 1.1 Product description The product is applicable for kitchen exhaust ventilation with a maximum constant airflow temperature of 120 °C. The product is a centrifugal thermo box fan with AC or EC motor, and a casing that is made from galvanized steel and has mineral wool as insulation. The product is supplied with built-in weather protection and a drain plug for condensation.
1.5 Name plate 1 2 3 4 5 6 7 8 10 9 11 12 13 1. Type designation: Product name, dimension and motor type. Refer to 1.5.1 Type designation page 2. 2. Current, A 3. Input power, W 4. Frequency, Hz 5. Certifications 6. Scannable code 1 7. Voltage, V 8. IP class, enclosure class 9. Insulation class 10. Serial number: part number/production number/production date 11. Nominal fan speed 12. Weight, kg 13.
Caution If you do not obey these instructions, there is a risk of damage to the product, other materials or the adjacent area. • Approved hearing protection • Approved protective gloves • Approved protective shoes • Approved work clothing Note: Information that is necessary in a given situation. 2.2 Safety instructions Warning Read the warning instructions that follow before you do work on the product.
3 Transportation and storage Warning Make sure that the product does not become damaged or wet during transportation. A damaged or wet product can cause fire or electric shock. 4 Installation 4.1 To do before the installation of the product • Make sure that you have the necessary installation accessories: – Refer to 13 Accessory overview page 23 for an overview of the accessories. • Before you move the product to the installation location, examine the packaging for damages.
4.2 1 To install the product Install the product on the mounting feet. Make sure that the weight of the product is equal on the mounting feet. Make sure the drain plug is at the lowest point of the product to drain the condensation. 4.2.1 1 Systemair recommends to use flexible connections or FK fast clamps to attach the duct to the product. Flexible connections and FK fast clamps are available as accessories. Risk of damage to the product if there is much water that cannot drain.
5 Electrical connection 5.6 5.1 To do before the electrical connection • If the product has an built in motor protection, reset by disconnecting the product from power for 60 seconds. • Make sure that the electrical connection agrees with the product specification on the motor name plate. • Make sure that the environment for electrical connection is clean and dry. • Make sure that the wiring diagram that is included with the supply of the product agrees with the terminals in the connection box.
6 Commissioning 7 Operation Caution Caution • If strong vibrations occur during commissioning, immediately increase or decrease the fan speed until the vibrations are decreased. Continuous strong vibrations can cause damage to components. EC motors must be set to ON/OFF via the control input. To stop the product via mains supply decreases the life time of the motor. Systemair recommends to install external speed controller for easy access to control the input signal.
8 Maintenance Warning Set the installed safety switch in the OFF position before you do the maintenance unless the instructions tell you differently. Make sure that the safety switch is not accidentally set in the ON position. 8.1 Maintenance schedule The intervals are calculated from continuous operation of the product. Maintenance task Usual operation conditions Each 6 months Each 3 months Each 6 months Visually examine the product and its components for damage, corrosion and dirt.
9 Troubleshooting Note: If you cannot find a solution to your problem in this section, speak to Systemair technical support. Problem Cause Solution The fan impeller is not correctly balanced. Speak to Systemair technical support. There is dirt on the fan impeller. Clean the fan impeller carefully. Refer to 8.2 To clean the product page 8. The fan impeller has damages or deformations because the transported air contains aggressive media. Speak to Systemair technical support.
Problem Cause Solution The fan impeller does not turn in the correct direction. Make sure that the electrical connection is correctly done. A phase loss occurred. If the motor is a 3-phase motor, make sure that no phase is missing. Note: This is not applicable for EC motors. The motor is overheated. Thermal contacts, PTC or resistors are released. • Do a check of the motor cooling impeller. • If it is possible, measure the resistance to do a check of the motor winding.
10 Disposal The product follows the WEEE directive. This symbol on the product or the packaging of the product shows that this product is not domestic waste. The product must be recycled at an approved disposal location for electrical and electronic equipment. 11 Warranty For warranty claims, send a written maintenance plan and the commissioning report to Systemair. The warranty is only applicable for these conditions: • The product is correctly installed and operated. • Motor protection is used.
12 Technical data 12.1 Technical data overview Maximum temperature of transported air, °C 120 Sound pressure, dB Refer to the data sheet in the online catalogue at www.systemair.com. IP class Voltage, current, frequency, enclosure class, weight Motor data 12.2 Refer to the name plate. Refer to 1.5 Name plate page 2 for more information. Refer to the motor name plate or the technical documentation from the motor manufacturer.
K A L B J C Q D I E H M F N G O P R J S T The dimensions are split over 2 separate tables.
Table 2 K L M N O P Q R S T KBT 160 100 43 100 209 470 473 345 437 54 320 KBT 180 105 43 95 218 470 483 366 470 54 320 KBT 200 115 43 113 233 470 617 392 510 54 440 KBT 225 121 43 121 251 620 635 412 522 54 440 KBT 250 140 43 139 272 620 656 436 576 54 440 KBT 280 155 43 139 293 620 677 462 625 54 440 L2 L3 12.3 Wiring diagrams The wires in the motor cables have these colours: Wire Colour +10V Red 0...
12.3.2 Wiring diagrams for EC fans KBT EC fans 1–phase 230 V KBT 160 EC A B L C N D NC E F BK BU YE/GN WH1 WH2 RD A. Mains supply, phase B. Neutral G H COM +10V 0-10V PWM GND YE BU C. Earth D. Alarm relay, brake for failure E. Alarm relay, COMMON F. Voltage output +10V max. 1.1 mA G. Control input (impedans kΩ) H. Ground KBT EC fans KBT 180 EC KBT 200 EC KL3 KL2 0-10V RS A RS B RS A RS B GND 0-10V PWM 4-20mA +20V +10V PWM GND A B C D E F A.
KBT EC fans KBT 225 EC KBT 250 EC KL3 12 11 10 9 8 7 6 5 I J K 4 3 2 RS A RS B RS A RS B GND 0-10V 4-20mA +20V +10V 0-10V GND A B C D E F G H KL2 3 1 2 1 KL1 3 2 1 L2 L3 OUT NO COM NC L1 L M N O P Q R P1 S 10k 0-10V A. RS485 interface for ebmBUS; RS A B. RS485 interface for ebmBUS; RS B C. RS485 interface for ebmBUS; RS A D. RS485 interface for ebmBUS; RS B E. Ground F. Control input G. Control/Actual value input H.
REE — Thyristor REE 1 and REE 2 - Surface mounting or with flush mounting casing included. REE 4 - Surface mounting. N Note: Starting currents must be considered when you select the speed controller type. Products that are used with this speed controller must have a built-in overheating protection and must be designed for thyristor speed control. N L (L) N N N L (L) N M M • L: the connection with cutting function on the speed control. • (L): the connection without cutting function.
A. Relay connection. There is always 230 V between ~ and N when the transformer knob is in one of the positions 1–5. B. Mains supply C. Earth D. Fan E. Thermostat F. Motor protection. If the motor protection is not in use, Tk must be looped together. FRQ5S-E-6A Frequency converter with built-in all-pole sine filter and 5-step switch. FRQ5S-E-6/10A 0 5 N N U1 U1 U2 U2 21 24 D1 A2 E1 TB D1 GND GND BU Digital In 1 22 K2 01 D PE L1 B N PE U1 U2 TB TB M 1~ q C A.
RTRD A 3-phase transformer that controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted by using the control knob on the front of the unit. RTRD2-7 N L L RT RT FS FS TK TK A A B N L1 L2 L3 N L1 L2 L3 U V W A 230 V AC PE U W TB TB C D A. If the function is not necessary, the terminals must be bridged B. Contact rating, 230 V AC/maximum 1 A PE M 3~ E 01 V Y/ F C. OFF/ON D. OFF/ON (only by reset) E.
RTRDU Manual 5–step transformer with motor protection — a 3–phase transformer that controls the fan speed by altering the supply voltage in five fixed steps. The steps are adjusted by using the control knob on the front of the unit. RTRDU A 0 B 0 5 15 4 24 3 1 1 2 3 2 3 N L L RT RT FS FS TB TB A A N L1 L2 L3 PE N L1 L2 L3 U V W A 230 V AC max. 1 A 230 V AC U F B 01 TB TB C D E A. If the function is not necessary, the terminals must be bridged B.
MTP 20 MTP 20 1/Vdc+ +10V 4/Vout 0...10V 2/Vdc- GND 3/Vout- EC-Basic EC-Basic 1/IN Vac 230V AC 2/IN Vac +10V 4/Out 0...10V 5/GND GND MTV–1/10 MTV 1/010 1/IN Vac 230V AC 2/IN Vac +10V 4/Out+ 0...10V 5/Out- GND S-5EC/FRQ MTP 10 10V +10V GND 0...10V A GND EC-Vent EC-Vent IN/RPM optional IN/10V OUT/PWN GND TACH +10V PWM 0...
12.3.5 Wiring diagrams for ON/OFF controls for EC motors CO2RT-R(-D) CO2RT-R-D Supply +10V Neutral 0...10V Common GND 24V AC Relay NO Relay NC Din1 IR24–P IR24-P 24V +10V Neutral 0...
13 Accessory overview 1 2 3 4 5 1. 2. 3. RSA: Silencer LRK: Airflow shutter UGF: Transition flange 4. 5. ASF: Flexible connection WBK: Wall bracket Note: For more information about accessories, refer to www.systemair.com or speak to Systemair technical support.
14 EU Declaration of Conformity We, the manufacturer Manufacturer Systemair Sverige AB Address Industrivägen 3 739 30 Skinnskatteberg Sweden declare under our sole responsibility that the products Type/Model KBT Identification Serial numbers dating from 2022 and onwards fulfils the relevant provisions of following directives and standards Machinery Directive 2006/42/EC EN ISO 12100:2010 Safety of machinery – General principles for design - Risk assessment and risk reduction EN ISO 13857:2019 Safet
15 UK Declaration of Conformity We, the manufacturer Manufacturer Systemair Sverige AB Address Industrivägen 3 SE-73930 Skinskatteberg Sweden declare under our sole responsibility that the products Type/Model KBT Identification Serial numbers dating from 2022 and onwards fulfils the relevant provisions of following directives and standards Supply of Machinery (Safety) Regulations 2008 EN ISO 12100:2010 Safety of machinery – General principles for design - Risk assessment and risk reduction EN ISO
last page Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg +46 222 440 00 mailbox@systemair.com www.systemair.com © Copyright Systemair AB All rights reserved EOE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.