Roof fans TFC 225-560 S/P Operation and Maintenance Instructions Document in original language | 206434 · A006 GB
© Copyright Systemair AB All rights reserved E&OE Systemair AB reserves the rights to alter their products without notice. This also applies to products already ordered, as long as it does not affect the previously agreed specifications.
Contents 1 2 3 4 5 6 7 EU Declaration of conformity..............................1 Warnings.......................................................2 Product information .........................................3 3.1 General ................................................3 3.2 Technical data .......................................4 3.2.1 Dimensions and weight ...............4 3.2.2 Performance .............................5 3.2.3 Wiring diagram ..........................6 3.2.
EU Declaration of conformity | 1 EU Declaration of conformity Manufacturer Systemair Sverige AB Industrivägen 3 SE-739 30 Skinnskatteberg SWEDEN Office: +46 222 440 00 Fax: +46 222 440 99 www.systemair.com hereby confirms that the following products: Roof fans TFC 225-560 S/P (The declaration applies only to product in the condition it was delivered in and installed in the facility in accordance with the included installation instructions.
2 | Warnings 2 Warnings The following admonitions will be presented in the different sections of the document: Danger Indicates a potentially or imminently hazardous situation which, if not avoided, could result in death or serious injury. Warning Indicates a potentially hazardous situation that may result in minor or moderate injuries. Caution Indicates a risk of damaging the product or prevent optimal operation.
Product information | 3 Product information 3.1 General This installation manual concerns Roof fans TFC 225, TFC 280, TFC 355, TFC 450, TFC 500 and TFC 560 manufactured by Systemair Sverige AB. The S-fans are delivered with potentiometer, 0-10 V. The integrated potentiometer is factory preset to 10 V. This value can be changed manually to obtain a different motor rpm/fan performance. Fan performance charts for this purpose are shown in the table by voltage steps (chapter 3.2.2).
| Product information 3.2 Technical data Dimensions and weight C F 3.2.
Product information | Performance 0 [m³/h] 600 900 300 1200 1440 TFC 225 400 500 1000 [m³/h] 1500 2000 2500 500 16738, 16737 600 0 16853, 16852 3.2.2 TFC 280 400 Ps [Pa] Ps [Pa] 300 200 200 100 2,6V 4,6V 0.1 0.2 Q [m³/s] 6,5V 10V 0 1000 2000 [m³/h] 3000 0.3 0.4 4000 5000 0.4 Q [m³/s] 0 2000 7,4V 10V TFC 355 500 [m³/h] 4000 0.8 6000 TFC 450 600 Ps [Pa] 750 0.6 800 16745, 16744 1000 400 200 250 2,5V 5V 0 0.4 0.
| Product information 3.2.3 Wiring diagram Modbus communication is possible from TFC 355, see wiring diagram.
PE L1 L2 L3 400V 3~ Ext = External GND BU 0-10V DC Ext 3 GN-YE BN BK GY GY BK BN GN-YE GN-YE BK 1 BK 2 BK 3 WH 1 WH 2 BN WH RSB RSA 3 GN-YE BN BK GY RD YE 0-10V DC Ext GY BK BN GN-YE PE L1 L2 L3 NC C RSB RSA 400V 3~ +10V PE L1 L2 L3 206434 | A006 Ain1U Product information | TFC 500 S 1 M TFC 560 S 1 2 1 4 3 6 5 2 1 4 3 6 5 M 7
| Product information TFC 225-280 P 1 2 Ri = 4 kΩ 1 4 3 GN-YE BN/BK BU WH YE BU 10V DC RD 2 1(+) 2( ) Tacho US GND A GND + - 10...24 V DC M PE 230V 1~ L N TFC 355-450 P 3 2 1 Ri = 4 kΩ US GND A GND 1 4 3 GN-YE BN BU BN BU GN-YE 10...
Product information | TFC 500 P 3 2 1 Ri = 4 kΩ 1(+) 2( ) 2 1 4 3 6 5 2 1 4 3 6 5 GN-YE BN BK GY GY BK BN GN-YE + - GN-YE BK 1 BK 2 BK 3 WH 1 WH 2 RSB WH BN YE BU RD 10V DC RSA US GND A GND 10...24 V DC M PE L1 L2 L3 400V 3~ TFC 560 P 3 2 1 Ri = 4 kΩ US GND A GND GN-YE BN BK GY 10...
10 | Installation 3.2.4 Residual current devices Only universal (type B, B+) RCD protective devices are permitted. Like frequency inverters, RCD protective devices cannot provide personal safety while operating the device, pulse charge currents from the capacitors in the integrated EMC filter lead to the RCD protective device triggering without delay. We recommend residual current devices with a trigger threshold of 300mA and delay triggering. (super-resistant, characteristic K) 3.
Installation | 4.1 Installing the fans Figure 1 Loosen the screws to open the lid to reach the motor. Unscrew the two screws to open the lid to the electrical compartment. Figure 2 Connect the mains supply to the lockable safety switch (1). Image show S-controller (2). The hinges on the hatch to the electrical compartment prevents the hatch from falling down. Figure 3 Possible to mount the TFC with suitable roof curb (optional), using the holes in the bottom of the fan (3).
12 | Installation 5 4 Figure 5 Mains supply (4) can be run through the cable glands beside the electrical compartment or inside a roof curb, if used. Note: Don’t cover this gap (5). It is for drainage if water enters the fan.
Installation | 4.2 Change from VAV to CAV TFC 225 -TFC 560 are delivered as VAV- fans. The tubing is connected to - (minus) inlet on the controller. All fans are also prepared with tubing for CAV (Constant air volume). The tubing is attached along the side of the casing and loosely inserted in the electrical compartment. Change the function to CAV by replacing the connection to the controller, the tubing from the bottom of the fan (1) to + (plus) inlet and the tubing from the cone (2) to - (minus).
14 | Installation 4.4 Commissioning Danger • All electrical connections must be carried out by an authorized installer and in accordance with local rules and regulations. Before initial operation, check the following: • Electrical connection has been properly completed. • Protective earth has been connected. • Safety devices in place (protection grid). • Leftover installation materials and foreign materials have been removed from the casing.
Control panel | 5 Control panel 5.1 Operating the control panel Multipurpose LC display and keyboard Display show the actual and desired values 100 Pa ∆p Display show menu text P Program key and open menu ▼ Menu selection, reduce value ▲ Menu selection, increase value ▼+▲ ESC-key combination, Escape = leave menu Messages on the display ! Exceeding measuring range Moon symbol = Adjustment for Setpoint 2 active Display after turning on the voltage supply.
16 | Control panel Select operation mode Marked area indicates factory setting. Mode Function 4.00 Pressure sensor output 0...10 V proportional to measuring range. 4.01 Factory preset Pressure controller (PID): Output 0...10 V depending on adjusted setpoint and measured actual value. 5.00 Air volume sensor: Output 0...10 V proportional to measuring range (depending on setting for K-factor). 5.01 Air volume controller (PID): Output 0...
Control panel | SETTING 4.01 + 5.01 1 2 Setting Setpoint 1 - 100 Pa - 1185 m3h Setpoint 1 1 Setpont 2 - 200 Pa - 1185 m3h Setpoint 2 1, 2 (Active if voltage at terminals 1, 2) Pband - 250 Pa - 1185 m3h Pband 1, 2 Min. Uout - 0.0 V - 0.0 V Min output voltage: 0.0...10.0 V (priority over “Max. Uout”) Parameter Display/factory setting Max. Uout - Function - 10.0 V 10.0 V Max. output voltage: 10.0...0.0 V Setting range 4.01: 0...100 % sensor measuring range, 5.01: 0...Max.
18 | Maintenance 6 Maintenance 6.1 Important Danger • Make sure that the mains supply to the unit is disconnected before performing any maintenance or electrical work! • Fan impeller has come to a complete standstill. • Should the supply cable be damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard • The unit is heavy. Be careful during transport and installation. Risk of injury through pinching. Use protective clothing.
Troubleshooting | Loosen the M5 screws to open the lid (chapter 4.1.) Unscrew the motor bracket's two screws. Lift the motor up by holding the motor bracket's handle, keep fingers away from the back of the hinge. Make sure that the motor bracket attach to the lock to prevent the motor from falling down during maintenance. After maintenance, release the lock, using the handle to bring the motor down. Fasten the motor bracket with the screws.
Phone +46 222 440 00 Fax +46 222 440 99 www.systemair.