OPERATION INSTRUCTIONS DSG PRESSURE SENSOR

5 Connection and operating elements
+Us / GND Supply voltage
A / GND Output signal 0...10 V
S1 Zero point button
V1 Status LED
S2 DIP switch measuring range
-
Minus- connection in area with lower
pressure
+
Plus- connection in area with higher
pressure
Danger due to electric current
Make sure that the supply voltage lies within the allowable tolerance specications
(
Technical data and the nameplate is xed to the side of the device).
Only PELV current sources which ensure safe electrical isolation of the operating
voltage in accordance with IEC/DIN EN 60204-1 must be used.
There is no potential isolation between supply voltage and output signal.
Pay attention to maintain sufcient distance from powerlines and motor wires to
prevent interferences.
The length of the cable for the output signal may be max. 30 m; it must be shielded
from 20 m! When using a shielded cable the shield must be connected (as short and
with as low an induction as possible!) to the PE conductor on one side at the signal
input (of the evaluation unit).
State LED V1
LED ashes every 2 seconds: Normal operation
LED lights constantly for 3 seconds: Zero point calibration is performed
LED ickers permanently: Sensor defective
Operating Instructions MPG-..V Connection and operating elements
L-BAL-E248-GB 1515 Index 001 Part.-No. 00163446
6/11