english POC-M Control module with integrated pressure sensor e.g. for central extraction systems Quick Start Guide Detailed Description on www.systemair.com Software version: from version 11.16 L-BAL-E231-GB 1446 Index 001 Part.-No.
Quick Start Guide POC-M Content 1 General notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 Structure of the short operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.2 Exclusion of liability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 3 3 2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Quick Start Guide POC-M 1 1.1 General notes General notes Structure of the short operating instructions Attention! This Quick Start Guide contains basic information on safety, use, installation and quick commissioning. The detailed Operating Instructions can be found on our website. The additional information they contain must be observed. Example: To download the Operating Instructions, go to www.systemair.com and search key enter the article number of the device as the search key ( name plate).
Quick Start Guide POC-M 2.3 Product overview Work on the device Information Mounting, electrical connection, and start-up operation may only be carried out by an electrical specialist in accordance with electrotechnical regulations (e.g. EN 50110 or EN 60204)! Danger due to electric current It is generally forbidden to carry out work on electrical live parts.
Quick Start Guide POC-M 4 4.1 Mounting Mounting General notes Attention! The following points must be complied with during the mechanical installation to avoid causing a defect in the device due to assembly errors or environmental influences: • • • • • • • • • • 4.2 Before installation remove the device from the packing and check for any possible shipping damage! Assemble the device on a clean and stable base.
Quick Start Guide POC-M 5 Electrical installation Electrical installation Information This Quick Start Guide does not list all connection options or notes for electrical installation (full Operating Instructions, connection diagram Enclosure). description 5.1 Mains connection Power from the mains is connected to terminals: PE, L1 and N. Here, it must be strictly observed that the mains voltage lies within the allowable tolerance specifications ( Technical data and nameplate affixed to the side).
Quick Start Guide POC-M 5.4 Electrical installation Digital inputs (D1, D2) Various functions can be allocated to the digital inputs “D1” and “D2” ( IO Setup: Functions summary of the digital inputs). Activation via floating contacts (a low voltage of ca. 24 V DC is connected). Factory setting for digital input “D1” : Switch over setpoint 1 / setpoint 2 (function = |5D | ) “Setpoint 1” with open contact / “setpoint 2” with closed contact. For operation with second control circuit: switch over “1.
Quick Start Guide POC-M • Start-up Pay attention to sufficient distance from powerlines and motor wires (min. 20 cm). The data line must be connected from one device to the next. No other type of wiring is allowed! Always use only two wires of one lead (twisted pair) for the connection. Further description 6 6.1 Operating Instructions Start-up Prerequisites for commissioning Attention! 1. You must mount and connect the device in accordance with the operating instructions. 2.
Quick Start Guide POC-M Start-up Excerpt from the menu table Start Language GB GB US units OFF OFF 4.01 4.02 Setpoint1 250.0 Pa 250.0 Pa Setpoint2 250.0 Pa 250.0 Pa Pband 1 250.0 Pa 250.0 Pa Min. Speed 0% 0% Max. Speed 100 % 100 % OFF OFF Base setup Mode Setting Manual mode Speed man. 100 % T-Band SA 100 % 30.0 K T-Start SA 15.0 °C Min Setpoint 70.0 Pa Information Adjust further settings according to the desired function ( L-BAL-E231-GB 1446 Index 001 Part.-No.
Quick Start Guide POC-M 7 Controls and Menu Controls and Menu 7.1 Multipurpose LC display and keyboard 2 34 5 6 7 8 9 10 11 13 2 1 Main menu 12 4 A B + 20.08.2014 v_display_erkl_cxe_modbus_master.vsd 1 A Actual value display Display after line voltage is switched on or after the Esc key combination is used to exit the settings menu (display depends on selected mode and sensor value). B Main menu Display after the Esc key combination is used to exit the actual value display.
Quick Start Guide POC-M 7.3 Controls and Menu Menu structure User ←←←← Info 0.0 Pa E1 Actual Esc Main menu ↔ Start Setting Protocol Base setup Controller Setup P↓ ↑ ESC ▲▼ Info Start ▼ Main menu ▲ Start Setting Protocol Base setup Controller Setup P↓ ↑ ESC Setting ▼ Main menu ▲ Start Setting Protocol Base setup Controller Setup P↓ ↑ ESC Protocol 1/22 PIN 0010 Service ▼ Main menu ▲ Start Setting Protocol Base setup Controller Setup P↓ ↑ ESC Base setup 18.6 °C E2 Actual ----PIN input 250.
Quick Start Guide POC-M 7.4 Controls and Menu Overview menu groups Main menu Possible settings Info Display measured actual values, selected setpoints, modulation, etc. Settings cannot be made in this menu group. Start PIN input for reset to initial settings and to protect settings. Setting the menu language. Display in SI units or Imperial units (US) Complete re-start of the device. Display of the set mode, software version, etc. Setting Protocol Settings for Operation, Setpoint, Pband, Min.
Quick Start Guide POC-M 8 8.1 Enclosure Enclosure Technical data Type POC-M Part-No. 313833 (320060-42) Line voltage 1 ~ 230 V (-15 % bis +10 %), 50/60 Hz Weight 0.98 kg Input resistance for sensor signal (E2) for 0 - 10 V input: Ri > 900 kΩ for input 4 - 20 mA: Ri = 250 Ω (max. load 500 Ω) Voltage supply for external devices +24 V (-30...
Quick Start Guide POC-M 8.2 Enclosure Connection diagram POC-M 7 J1 Kontaktbelastung Contact rating max. AC 250 V 2 A L1 N PE 11 14 K1 12 21 24 22 1A 1B 2A (1D+) (1D-) (2D+) ID GND 2B (2D-) Digital In 1/2 24 V DC Out Analog Out 1/2 D1 24V A1 D2 GND A2 Analog In 1/2 TF In 1/2 GND E1 T GND E2 T USB 6 Drucksensor Pressure sensor 0...500 Pa K2 L1 N PE Netz Line 1 ~ 230 V 50/60 Hz 1 Addressing + ∆p TF..
Quick Start Guide POC-M 8.4 Enclosure Manufacturer reference Our products are manufactured in accordance with the relevant international regulations. If you have any questions concerning the use of our products or plan special uses, please contact: Systemair Industrievägen 3 73930 Skinnskatteberg Telefon:+46 (0) 222 440 00 Telefax:+46 (0) 222 440 99 mailbox@systemair.se www.systemair.se L-BAL-E231-GB 1446 Index 001 Part.-No.