VLSP SD230 TAC BPV10 AV VLSP VKF TAC AV BPV10 SE .... 2 EN .... 9 NO .... 16 DE .... 23 NL .... 37 ES .... 44 RU .... 51 PL .... 58 SD230 FR ....
VLSP EN Components VLSP, pressure independent valve system on/off VKF TAC (TA Compact-P) AV BPV10 SD230 VLSP15LF Type TAC15LF SD230 AV15 BPV10 Specification Two way pressure independent regulation and adjustment valve Actuator on/off 230V Shut off valve By-pass valve Low flow, DN15 230V~ DN15 DN10 VLSP15NF Type TAC15NF SD230 AV15 BPV10 Specification Two way pressure independent regulation and adjustment valve Actuator on/off 230V Shut off valve By-pass valve Normal flow, DN15 230V~ DN15 DN10 VL
EN VLSP VLSP, pressure independent valve system on/off Two way pressure independent control and adjustment valve with on/off actuator, shut-off valve and bypass. DN15/20/25/32. 230V. The valve set consists of the following: • TAC, pressure independent regulation and adjustment valve • SD230, actuator on/off 230V • AV, shut off valve • BPV10, bypass valve The shut off valve (AV) consists of a ball valve which is either open or closed and is used to shut off the flow, when servicing for example.
VLSP EN Two way pressure independent regulation and adjustment valve TAC (TA Compact-P) Dimensions and technical specifications L ØB H1 D H2 Da M30x1.
EN VLSP Leakage rate: Leakage flow ≤ 0,01% of max. qmax (setting 10) and correct flow direction. (Class IV according to EN 60534-4). Connection: Male thread according to ISO 228. Marking TA, IMI, PN 16, DN and flow direction arrow. Grey setting wheel: TA-COMPACT-P and DN. For low flow version also LF. Application The regulation and adjustment valve (TAC) can be used to finely adjust or shut off the water flow manually.
VLSP EN Setting Shut-off 1. Turn the setting wheel to desired value, e.g. 5.0. 1. Turn the setting wheel clockwise to X. Measuring accuracy Sizing Maximum flow deviation at different settings. 1. Choose the smallest valve size that can obtain the design flow with some safety margin, see “qmax values”. The setting should be as open as possible. 2. Check that the available ΔpV is within the working range 15-400 kPa or 23-400 kPa.
VLSP EN Closing force Working range: X (closed - fully open) = 11,6 - 15,8 Closing force: Min. 125 N (max. 500 N) Ø22 The maximum recommended pressure drop over a valve and actuator combination for close off (ΔpVclose) and to fulfill all stated performances (ΔpVmax). DN15 DN20 DN25 DN32 10 kPa* 400 400 400 400 M30x1,5 *) Closing force 125 N.
VLSP By-passvalve (BPV10) Dimensions and technical specifications Type BPV10 HxWxD [mm] 63x45x28 Weight [kg] 0,17 EN On/Off-regulation, linear motion Supply voltage 230V, 50-60 Hz Power consumption <1,5 VA in operation <0,5 VA in the end position Stroke force 100 N Stroke length 6,5 mm Full stroke time "On" Nominal 3 s Full stroke time "Off" Nominal 12 s Protection class IP54 Screw-nut M30x1,5 Cable length 1,5 m Isolation class II Surrounding temp.
Tel: +46 31 336 86 00 mailbox@frico.se www.frico.net For latest updated information and information about your local contact: www.frico.net.