DXRE 172390 04

5
DXRE
To t the droplet eliminator
Droplet eliminator DE must be installed downstream of the
cooling coil in the duct cooler.
Fitting is done according to seperate instruction.
Cleaning
In order to ensure full capacity of the duct cooler, the nned coil
and droplet eliminator, if tted, must be regularly cleaned. e
intervals between cleaning are entirely dependent on the clean-
liness of the air and on how well the lter and the remainder of
the system are maintained.
CAUTION. Make sure there is no one below the drip tray when
it is being removed.
Modell B mm H mm S mm R mm I mm O mm K mm M mm
N
mm
C
Coil inside
volume, l
DE
DXRE 400x200-3-2,5 438 238 56 105 60 95 165 51 19 1/2 0,81 DE 40x20
DXRE 500x250-3-2,5 538 288 56 105 60 50 165 41 22 1/2 1,23 DE 50x25
DXRE 500x300-3-2,5 538 338 56 105 60 50 165 54 22 1/2 1,48 DE 50x30
DXRE 600x300-3-2,5 638 338 56 105 60 50 165 54 22 5/8’’ 1,72 DE 60x30
DXRE 600x350-3-2,5 638 388 56 105 60 50 165 54 22 5/8’’ 2,00 DE 60x35
DXRE 700x400-3-2,5 738 438 56 115 110 50 160 60 35 5/8 3,25 DE 70x40
DXRE 800x500-3-2,5 838 538 86 115 140 50 160 60 35 5/8’ 4,53 DE 80x50
DXRE 1000x500-3-2,5 1038 538 86 115 140 50 160 60 35 5/8’ 5,46 DE 100x50
Remove the condensate outlet and blank o the connector so
that any remaining condensate will not run out. Remove the
drip tray by releasing the excentric lock on the front. Lower the
drip tray about 2 – 3 cm and then move it towards the back so
that the locking mechanism at the back will be released. e
drip tray is held captive by hinges the rear, but it can easily be
released to enable it to be removed from the cooler. If a droplet-
eliminator is tted, push the holder to the side and remove the
droplet eliminator for cleaning with compressed air or warm
water. Use a soft brush to clean the inlet side of the coil, and
the entire coil can then be cleaned with compressed air or by
vacuum cleaning. Blow the dirt away in a direction away from
the air outlet side and towards the inlet side. Take care not to
deform the edges of the ns. Clean the bottom of the drip tray,
and check that no dirt is lodged in the condensate outlet.
en ret the droplet eliminator, drip tray and anti-condensa-
tion insulation.