UserManual FGS201811 en GB

10/22 | User Manual FGS | 201811
Electrical Connections
IMPORTANT: Danger of electric shock!
Switch off the power supply before working on any electrical equipment.
Only qualied electricians are allowed to work on the electrical system.
Tab. 4: Electric parameters of the microswitches and actuators based on the type of activation
Activation Type Electric Equipment Power Supply Electric Parameters
ZV None - -
DV1
Microswitch (Closed) AC 125/250 V 5A
Microswitch (Open) - -
DV1-2
Microswitch (Closed) AC 125/250 V 5A
Microswitch (Open) AC 125/250 V 5A
DV7-T
Actuator Belimo
AC 230 V, 50/60 Hz
Tab. 5DV9-T
AC (50/60 Hz)/DC 24 V
DV9-T-ST
Tab. 5: Electric parameters of Belimo actuators for FGS based on the type of activation mechanism
Type/Power
Consumtion
L (mm)
200 300 400 500 600 700 800
H
(mm)
200
300
400
500
600
700
800
900
1000
DV7-T/6,5 VA
DV9-T/4 VA
DV9-T-ST/11 VA
DV7-T/10 VA, DV9-T/6 VA, DV9-T-ST/11 VA