6.2 Location Dimensions
Figure 3: Minimum distances
NOTE
The indicated distances are minimum distances.
" Ensure the minimum distances for maintenance and service.
6.3 Preparation
The Combi Unit Genius is very compact. The unit is placed on teon sliders ensuring sound insulation and easy positioning. Adjustable
feet are not used to avoid rocking due to balance point shifting.
6.3.1 Installation Place
NOTE
Ensure a professional noise reduction of the unit.
" Use suitable sound insulation mats.
" Install the unit in a frost-free room on a load-bearing oor. The oor must be horizontal, level, solid and durable.
" Place the unit only on a oating screed when this is done properly.
" Also take the weight of the device including the content of the water tank into account.
" Align the unit exactly to ensure a safe condensate drain.
" Level the combi unit, if necessary place e.g. sound insulation strips under the unit.
RECOMMENDATION
" Install the complete heating/cooling unit not directly below, above or next to living rooms or bedrooms.
If the room conditions require disassembly of the combi unit see „6.4.1 Disassembly“ page 19.