Installation , Operation and Maintenance Instructions Genius
6.4 Location
6.4.1 Disassembly
Disassemble the modules only if the combi unit can not be transported as a complete unit to the installation place. The total height incl.
pallet is approx. 2.20m.
TIP
Dismount previously the 4 side panels of the ventilation module.
" Remove the front and rear panel from the hinges.
" Unscrew the side panels from inside.
Remove ventilation module
The ventilation module is only placed on the basic / heat pump module and can slide out due to tilting.
WARNING
Risk due to falling parts!
The side panels of the basic module are locked with hasps but not xed. They can fall down after loosening the screws.
» Hold the panels during loosening and put it down to the oor.
" Remove the left side panel of the basic module (access to the plug).
" Hold the side panel and remove it.
" Disconnect the 3 plug connectors in the upper part.
" Remove the module.
" Lead the plugs through the cover opening.
Pull out the heat pump module
The heat pump module is connected to the storage unit by 2 detachable, at sealing con-
nections 1“. The heat pump module is connected to the control cabinet with 4 plugs.
" Unscrew both doors.
Caution: First empty the pipes.
" Disconnect the two connections below the heat pump module.
" Disconnect the plug below the heat pump module on the left side.
" Disconnect the expansion valve plug connection on the board. For precise information
please refer to the electric wiring diagram.
" Loosen screws M6 on the front of the left and right guide rails with an allen key.
The support of the heat pump module is lowered by approx. 1.5 cm.
" Pull out the lowered module.
Figure 4: Disassembly
19
Genius - V 1.0
Assembly