Installation , Operation and Maintenance Instructions Genius

Filter alarm: B-Alarm
Meaning:
Reset lter life value reached (see Settings).
NOTE
All functions of the combi unit remain active during this alarm.
Remedying faults
" Change the lter. New lters can be obtained from Systemair.
" Reset lter life (see Settings).
" Select the alarm.
" Click the symbol Conrm.
Communication error room: B-Alarm
Meaning:
Communication error between room controller and the corresponding room. However, the unit function remains functional.
Remedying faults
" Fix the alarm or let it be xed by a service technician.
" Select the alarm.
" Click the symbol Conrm.
Manual operation: C-Alarm
The fans can be controlled manually, but only from the Service level.
Sensor error: B-Alarm
The unit operation continues after blocking of the alarm.
Pressure monitoring: C-Alarm
An external safety feature has been triggered due to an underpressure (wood-burning stove etc.). The system is locked. It will unlock by
itself after a monitoring period.
See also „4.2 Operation in Combination with Room Air Independent Fireplaces (Furnace Function)“ page 13.
36
Maintenance / Remedying Faults
Genius - V 1.0