Installation , Operation and Maintenance Instructions Genius

ResetFilterChangeandconrm.
" Reset lter life (see Settings).
" Select the alarm.
" Click the symbol Conrm.
8.3 Heat Pump Module
A refrigerant circuit maintenance is not necessary. Due to weather-related inuences, the evaporator ns must be checked from time to
time.
" Check the evaporator depending on installation place and suction height of the working air (recommended once a year).
" Check the evaporator for contaminations (once a year).
" Clean the condenser ns when contaminated.
Figure 14: Condenser ns
Condenser cleaning
WARNING
Danger electrical voltage!
» During cleaning, the entire unit must be disconnected from the mains!
» Observe the 5 Security Rules!
" Disconnect the both rear-sided air intake and outlet ducts from the unit.
" If necessary, clean the evaporator on the right intake in dry state, preferably with compressed air (caution against possible contami-
nation in the room).
Check and maintenance of the condensate drain
Check and maintenance interval: once a year
Condensate drain hoses are located below the individual air chambers in the heat pump module to drain condensate from the evaporator
in heating or cooling mode.
There are 5 condensate drains in all, which are provided with hoses:
2 connections each in the intake and discharge chamber of the working air, inlet and outlet chamber of the secondary air,
1 connection in the chamber of the cooling circuit.
The condensate hoses are each mounted below the individual chambers by means of hose clamps.
WARNING
Risk due to falling parts!
The panels are not xed. They can fall down after loosening the screws.
Hold the panels during loosening and put it down to the oor.
" Remove the left and front panel.
39
Genius - V 1.0
Maintenance / Remedying Faults