Installation , Operation and Maintenance Instructions Genius

" Unlock the two fasteners at the side panel.
" Remove the side panel.
" Check the condensate hoses for proper xation and for dirt.
Condensate hose cleaning
" Loosen the hose clamps on the heat pump module to remove clogged or heavily contaminated condensate hoses.
" Clean the condensate hoses.
" Attach the condensate hose with the hose clamps on the heat pump module.
8.4 Hot Water Module
8.4.1 Membrane Expansion Tank
1 Flexible hose connection
2 Filling valve
3 Expansion tank support
Figure 15: Membrane expansion tank
Check the primary pressure of the expansion tank.
Factory setting primary pressure: 1 bar.
" Remove the protection cap from the lling valve.
" Depressurise the water-bearing side by the ll and drain valve.
" Check the pressure of the expansion tank with a pressure gauge.
" Fill the connecting pipes as described in section „7.2.3 Connecting Pipes (ll/ush storage charging circuit)“ page 25.
In case of a fault
" Disconnect the ex pipe connection in unpressurised state (1)
" Open the bracket of the expansion tank (3).
" Change the diaphragm expansion tank.
8.4.2 SacricialAnode
Inspection interval: every 2 years
Figure 16: Sacricial anode (1)
The glassed domestic hot water tank is equipped with a magnesium anode to prevent corrosion.
Inspectionofthesacricialanode
Makesurethesacricialanodeisfreefromdefects.
40
Maintenance / Remedying Faults
Genius - V 1.0