Installation , Operation and Maintenance Instructions Genius

WARNING
Danger electrical voltage!
» The entire unit must be disconnected from the mains during check and replacement!
» Observe the 5 Security Rules!
The condition of the sacricial anode can be veried by a protective current measurement with an amperemeter.
Procedure:
" Remove the front and the left panel to access to the storage tank.
" Lift the black tank cover
" Remove the black tank cover and the sealing.
Access to the anode connection 1 ¼“.
" Disconnect the potential equalisation cable from the tank.
" Connect an amperemeter between anode and tank.
With a protective current of < 0.3 mA, the anode must be removed, checked for erosion and replaced if necessary!
" If the sacricial anode is highly corroded and nearly disintegrated, change the anode.
(Sacricial anode change see Service)
41
Genius - V 1.0
Maintenance / Remedying Faults