Installation , Operation and Maintenance Instructions Genius

Emergency operation You can maintain a reduced, temporary heating operation during a heat pump failure.
The function can only be activated manually and during heat pump alarm to avoid
operating errors.
The emergency operation is fully functional even when the PTC function is switched
off.
Settings: Yes / No
Default setting: No
Setpoint emergency operation The emergency operation of the heating function is ensured by the electric heating
elements (PTC). This function can only be switched on manually with an active heat
pump alarm. Once the fault is removed, the function will be reset.
The new emergency operation setpoint is valid independently of the setpoint tem-
perature in normal operation, see Unit.
Adjustment range: 18 °C ... 22 °C
Default setting: 18 °C
NOTE
If PTC elements are not used (e.g. passive house), the corresponding parameters will have no function.
10.4.4 Furnace Function - Operation in Combination with Room Air Independent Fireplaces
In this constellation, the heating fan can be manually controlled even without heating demand of the heat pump.
WARNING
Poisoning by exhaust fumes!
In parallel operation of a ventilation system and an air-ventilated replace, negative pressure can lead exhaust gases
into the rooms.
» Install and operate the Combi Unit Genius only together with an air-ventilatedreplace according to DIN 18897-
1:2005!
NOTE
The furnace operation may only be switched on and off manually.
The combi unit assumes the complete heating function. A shutdown must therefore be avoided.
Furnace operation Status Note
Off
Step 1 Capacity 60 %
Steps 1, 2 and 3 switch to Off automatically after two
hours.
Step 2 Capacity 80 %
Step 3 Capacity 100 %
10.4.5 Room Temperatures
Room 1 Living room
Status Active
PTC element blocked
Actual value temperature 22.5 °C
Setpoint value temperature 22.0 °C
PTC output 0 %
Display illumination standby 10 %
Display illumination normal 30 %