Installation , Operation and Maintenance Instructions Genius

10.6.4 Analogue Outputs
The fans operate with 0 ... 10 V. The actual performance can be derived by these outputs.
Example: 5 volts correspond 50 % power, 7 volts correspond 70 %.
Analogue outputs Voltage
AA1 Supply air fan control 6.0 V
AA2 Extract air fan control 5.5 V
AA3 Secondary air fan control 0.0 V
AA4 preheater 0.0 V
10.6.5 Digital Outputs
Actual components status (On/Off).
Digital outputs Temperature
DA1 Off
DA2 Off
DA3 Off
DA4 Rotor On/Off On
DA5 Sum alarm Off
DA6 Storage charge pump Off
DA7 Heating rod HW Off
DA1 Relay heat pump operation see Settings
DA2 Change-over After the switch-off point has been reached (see Settings), the signal switches.It can
be used as a switch for a second heat source.
DA3 Bypass cooling This output enables a passive cooling of a room. During commissioning, this room
must be dened as Room 2. If the current temperature of this room is higher than the
predened setpoint, this output will switch.
This triggers a relay which switches on a fan (to be installed by the client on-site).
The fan transports cool external air into the room via a bypass pipe.
58