Installation , Operation and Maintenance Instructions Genius
Heating: Setpoint after rotor alarm
Setpoint after rotor alarm The passive heat recovery is deactivated after rotor alarm (see section 8.1). Thus,
the efciency of the combi unit is negatively affected. Therefore, the (average) room
temperature setpoint is forced to reset during the alarm. The unit returns to the pre-
vious set mode
• after alarm remedy and conrmation;
• after alarm block without remedying faults.
Adjustment range: 18 °C ... 22 °C
Default setting: 19 °C
Heating
... ...
Temperature rotor alarm 19 °C
NOTE
Blocking of alarms can cause uncontrollable malfunctions.
" Use this function only in exceptional cases and after consulting specialised personnel.
Control parameters
Control parameters
Room controller
Actual value 21.5 °C
Setpoint 21.8 °C
Control output 43 °C
P-band 3 °C
I-time 20 s
Sup.air temp.con
Actual value 37.1 °C
Setpoint 43.0 °C
Control output 100 %
P-band 70 °C
I-time 30 s
min. supply air temp. 16.5 °C
Supply air control type Automatic
Max. Sup.air temp.man. 40.0 °C
Max. Sup.air temp.auto
Setpoint at (-15) 48 °C
Setpoint at (-5) 44 °C
Setpoint at (5) 40 °C
Setpoint at (15) 36 °C
Offset (-5 up to +5) 0°C
HP starts with a request > 30 %
69
Genius - V 1.0
Operation/Control via Internet/App