Installation , Operation and Maintenance Instructions Genius

10.8.1.2 Hot Water
Hot Water
Start charge pump if HW temp. < S... 1 °C
Stop charge pump if HW temp. > S... 2 °C
Extended running pump 150 s
Default value time program Automatic
Start/Stop charge pump Start/Stop charge pump describes the hot water generation hysteresis. Default set-
ting: 3 °C; i.e. with a default setting of the hot water temperature with 45 °C, the
heat pump and the storage charge pump start at a temperature of 44 °C and end the
generation at 47 °C.
Extended running pump The pump continues running for 150 seconds so that the heat pump can release all
the heat.
Hot Water
Default value time program Automatic
Ú
Automatic
Individual
Default value time program (see 10.7.2 Time Program)
PTC activation
PTC
PTC function Off
PTC start delay 45 min
PTC defrost power HP 20 %
Switch-off point -20 °C
Setpoint preheater -10 °C
P-Gain preheater 2
NOTE
The PTC function is deactivated in the factory.
During cooling circuit defrost, the elements will also be activated when switched off.