Installation , Operation and Maintenance Instructions Genius

Activated night cooling
Night cooling activated When night cooling is enabled, the speeds will automatically be increased during a
xed period of time (see Service, Settings). Thus, the air ow and the cooling capac-
ity increases.
The following factors are preset for the Activated night cooling:
The function is active when the average outdoor temperature was higher than 22
°C from 12:00 to 17:00.
The function is active from 24:00 to 6:00.
The function remains active at night with outdoor temperatures between 5 °C and
18 °C. Below or above it is interrupted.
The function is terminated when the average room temperature in the house falls
below 20 °C.
These factory settings can be adjusted on demand, the fan request below the Speed.
Setting:
no settings required
Default setting: 85 %, speed level for
supply and extract air fan
NOTE
A passive cooling by the rotary heat exchanger can only provide a relatively low temperature reduction. It can not
replace active heat pump cooling.
10.8.1.4 Filter alarm
Filter alarm
Reset lter life No
Number of months for lter change 12
Number of months since last lter change 1
At the end of the set months for lter change, an alarm message appears (see Alarm status). Once the lter has been changed, the func-
tion must be reset. The alarm remains visible even when it has been conrmed.
Resetlteralarm
The alarm remains active until the lter life is reset. No conrm response.
" Change the lter (see Filter Change).
" Set Reset lter life to Yes.
" Acknowledge lter alarm at Alarm status.
» The lter alarm is now reset. Number of months since last lter change is set to zero.
Filter alarm
Reset lter life Yes
Ú
Number of months for lter change No
Number of months since last lter change Yes
NOTE
Shows the number of months for lter changes:
a) down, if the lter is heavily contaminated.
b) up, if the lter still has a very good quality, max. 12 months.
10.8.1.5 E-mail
e-mail
Alarms via e-mail No
e-mail address
76
Operation/Control via Internet/App
Genius - V 1.0