Installation , Operation and Maintenance Instructions Genius

Setpoint room temperature
Setpoint room temperature 20.0 °C
Temperature rise + 3 °C
Temperature setback - 3 °C
Use this setting to specify the minimum and maximum setpoints of each room.
Factory settings: 20 °C / ±3 °C each.
This means that the room temperature setpoint can be set below the Actual value/Setpoint and as well as at the room controller
between 17 °C and 23 °C. If other values are desired for individual rooms, the rst room denition needs to be changed.
-Proportionalband(P-Band),Integraltime(I-Time)
P-band 3 °C
I-time 20 s
These parameters dene the action of the PTC elements of the individual room.
The PID controllers are preset and need normally no adjustment. If changes must be made, this must be carried out only by qualied
personnel.
Room designation
Room designation Living room
Any room / zone can be specied. These designations are transferred to the other tab pages.
Window contact
NO/NC Via a window contact, each room controller is able to activate a motorised
shut-off valve (Accessories), for example, in the bedroom. If the window is
opened, the valve closes and interrupts the air supply to this room; and with
it the heating function.
Via the Option NO/NC, this logic can be reversed if necessary, depending on
the design of the contact or the valve.
If the window contact function is activated, the status display will be shown
under Actual Value/Setpoint.
79
Genius - V 1.0
Operation/Control via Internet/App