Installation , Operation and Maintenance Instructions Genius

Holidays Holiday (MM:DD)
1: 01-01 - 01-01
2: 01-01 - 01-01
3: 01-01 - 01-01
Summer/Winter time
...
Holiday (MM:DD)
19: 01-01 - 01-01
20: 01-01 - 01-01
21: 01-01 - 01-01
Summer/Winter time Automatic summer/
Summer/Winter time: Yes
Service settings Supply air temperature Heating/cooling: Auto Cooling
Outdoor temp. > 26 °C
Heating
Outdoor temp. < 20 °C
Access Rights Heat pump Hot Water Cooling Mode setp.
Cooling Mode setp. Type of Setpoint:
Outdoor temp. Managed
Setpoint cooling curve
32= 26 °C, 28= 24 °C
30= 25 °C, 26= 23 °C
Shift: 0 °C
Heating Mode setp. Type of Setpoint:
Outdoor temp. Managed
Setpoint heating curve
-20= 23 °C, 0= 21 °C
-10= 22 °C, 15= 20 °C
Shift: 0 °C
Room temp. Reduce by:
0 °C in setback operation
Holiday mode temp.: 18 °C
Rotor alarm temp.:
19 °C
max./min. Supply air temp.
min.: 16.5 °C
Max.: Automatic
max. supply air temperature
Auto
-15= 52 °C, 5= 44 °C
-5= 48 °C, 15= 40 °C
Shift: 0 °C
92
Control via Display
Genius - V 1.0