SAVE VSR 300 500 SERVICE AND ACCESSORIESV01 1 12 0

Configuration |
21
Only available for Room temperature control / Extract air temperature control modes.
ECO mode
Configure ECO mode settings. Set heater offset. Default setting is 5°C.
Range: 0–10°C.
Fan Control
Configure airflow and fan settings. Select fan control (airflow) type. Default setting is Manual (%).
Available types: Manual (%) / Manual rpm / Flow (CAV) / Pressure (VAV) / External
Setting
Manual RPM Flow (CAV)
Pressure
(VAV)
External
Airflow
measurement
unit.
%
rpm
l/s, m
3
/h, cfm
Pa %
P-Band
0–3000 rpm 0–500 Pa
Default setting: 150 Pa
I-time
-
Off / 1–240 sec.
Default setting: 5
sec.
Off / 1–240 sec.
Default setting: 5 sec.
Airflow level
settings for each
level: MAXIMUM
LEVEL, HIGH
LEVEL, NORMAL
LEVEL, LOW
LEVEL,
MINIMUM LEVEL
16-100% 500–5000 rpm
Sensor range (airflow unit)
0–100%
Manual Fan Stop turn on or off manual fan stop, this function enables manual fan stop from HMI. Default setting
is OFF.
Pressure
Sensors
configure sensor
voltage relation
to pressure.
Set value at
which fan alarm
occurs. Default
setting is None
- -
Supply air fan control sensor:
Pressure at 0V: 0-500 Pa, default
setting 0 Pa
Pressure at 10V: 0-2500 Pa, default
setting 500 Pa.
Extract air fan control sensor:
Pressure at 0V: 0-500 Pa, default
setting 0 Pa.
Pressure at 10V: 0-2500 Pa, default
setting 500 Pa
-
Set K factor for
supply air fan
and extract air
fan. Default
settings are
based on unit
type.
- - SAF K-Factor
range: 0–1000
EAF K-Factor
range: 0–1000
- -
Outdoor
Compensation
A purpose of this function is to protect the unit from freezing by creating an unbalanced airflow
at extreme winter temperatures or to limit supply of cold/hot outdoor air at extreme winter/
summer conditions with balanced ventilation.
Function operates by lowering the speed of supply air fan (SAF) or both supply and extract air
fans (SAF/EAFC) by value set in Stop Compensation Value setting (adjustable from 0% to
50%) if the outdoor air temperature (OAT) drops below adjustable value set in Start
Compensation Temperature setting (during winter from 0 °C to -30 °C / during summer
from 15 °C to 30 °C). This compensation reaches the maximum as soon as the outdoor air
temperature reaches the adjustable value set in Stop Compensation Temperature setting
(during winter from 0 °C to -30 °C / during summer from 15 °C to 30 °C)
| v1_1.12.0