FC101 Design Guide
8.4 General Technical Data
Protection and features
•
Electronic motor thermal protection against overload.
•
Temperature monitoring of the heat sink ensures that the frequency converter trips if there is overtemperature.
•
The frequency converter is protected against short circuits between motor terminals U, V, W.
•
When a motor phase is missing, the frequency converter trips and issues an alarm.
•
When a mains phase is missing, the frequency converter trips or issues a warning (depending on the load).
•
Monitoring of the DC-link voltage ensures that the frequency converter trips when the DC-link voltage is too low
or too high.
•
The frequency converter is protected against ground faults on motor terminals U, V, W.
8.4.1 Mains Supply (L1, L2, L3)
Supply voltage 200–240 V ±10%
Supply voltage 380–480 V ±10%
Supply voltage 525–600 V ±10%
Supply frequency 50/60 Hz
Maximum imbalance temporary between mains phases 3.0% of rated supply voltage
True power factor (λ) ≥0.9 nominal at rated load
Displacement power factor (cosφ) near unity (>0.98)
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H1–H5, I2, I3, I4 Maximum 1 time/30 s
Switching on the input supply L1, L2, L3 (power-ups) enclosure sizes H6–H10, I6–I8 Maximum 1 time/minute
Environment according to EN 60664-1 Overvoltage category III/pollution degree 2
The unit is suitable for use on a circuit capable of delivering not more than 100000 A
rms
symmetrical Amperes, 240/480 V
maximum.
8.4.2 Motor Output (U, V, W)
Output voltage 0–100% of supply voltage
Output frequency 0–400 Hz
Switching on output Unlimited
Ramp times 0.05–3600 s
8.4.3 Cable Length and Cross-section
Maximum motor cable length, shielded/armored (EMC-correct installation) See chapter 3.4.3 EMC Emission Test Results
Maximum motor cable length, unshielded/unarmored 50 m (164 ft)
Maximum cross-section to motor, mains
1)
Cross-section DC terminals for lter feedback on enclosure sizes H1–H3, I2, I3, I4 4 mm
2
/11 AWG
Cross-section DC terminals for lter feedback on enclosure sizes H4–H5 16 mm
2
/6 AWG
Maximum cross-section to control terminals, rigid wire 2.5 mm
2
/14 AWG
Maximum cross-section to control terminals, exible cable 2.5 mm
2
/14 AWG
Minimum cross-section to control terminals 0.05 mm
2
/30 AWG
1) See chapter 8.2.2 3x380–480 V AC for more information.
General Specications Design Guide
MG18C822 Danfoss A/S © 04/2018 All rights reserved. 119
8 8