FC101 Programming Guide

No. Description Warning Alarm Trip Lock Parameter Reference
32 Motor phase W missing (X) (X) Parameter 4-58 Missing Motor
Phase Function
38 Internal fault X X
44 Ground fault 2 X X
46 Gate drive voltage fault X X
47 24 V supply low X X
50 AMA calibration failed X
51 AMA check U
nom
and I
nom
X
52 AMA low I
nom
X
53 AMA motor too large X
54 AMA motor too small X
55 AMA parameter out of range X
56 AMA interrupted X
57 AMA time-out X
58 AMA internal fault X X
59 Current limit X
60 External interlock X
66 Heat sink temperature low X
69 Power card temperature X X X
79 Illegal PS cong X X
80 Frequency converter initialised to default value X
84 LCP error X
87 Auto DC brake X
92 No-Flow (X) (X) Parameter 22-23 No-Flow
Function
95 Broken belt X X Parameter group 22-6* Broken
Belt Detection
99 Locked rotor X X
126 Motor rotating X
127 Back EMF too high X
201 Fire mode X
202 Fire mode limits exceeded X
250 New spare parts X X
251 New type code X X
Table 4.1 Alarm/Warning Code List
(X) Dependent on parameter
A trip is the action when an alarm has appeared. The trip coasts the motor and can be reset by pressing [Reset] or via a
digital input (parameter group 5-1* Digital Inputs [1]). The original event that caused an alarm cannot damage the frequency
converter or cause dangerous conditions. A trip lock is an action when an alarm occurs, which may cause damage to the
frequency converter or connected parts. A trip lock situation can only be reset by a power cycling.
Warning yellow
Alarm ashing red
Table 4.2 LED Indication
The alarm words, warning words, and extended status words can be read out via eldbus or optional eldbus for diagnosis.
See also parameter 16-90 Alarm Word, parameter 16-92 Warning Word, and parameter 16-94 Ext. Status Word.
Troubleshooting Programming Guide
MG18B502 Danfoss A/S © 04/2018 All rights reserved. 99