FC101 Programming Guide

3.12.7 16-9* Diagnosis Read-Outs
16-90 Alarm Word
Range: Function:
0* [0 - 0xFFFFFFFFUL ] View the alarm word sent via the serial
communication port in hex code.
16-91 Alarm Word 2
Range: Function:
0* [0 - 0xFFFFFFFFUL ] View the alarm word 2 sent via the
serial communication port in hex code.
16-92 Warning Word
Range: Function:
0* [0 - 0xFFFFFFFFUL ] View the warning word sent via the
serial communication port in hex code.
16-93 Warning Word 2
Range: Function:
0* [0 - 0xFFFFFFFFUL ] View the warning word 2 sent via the
serial communication port in hex code.
16-94 Ext. Status Word
Range: Function:
0* [0 - 0xFFFFFFFFUL ] Shows the extended status word sent
via the serial communication port in
hex code.
16-95 Ext. Status Word 2
Range: Function:
0* [0 - 0xFFFFFFFFUL ] Shows the extended status word 2 sent
via the serial communication port in
hex code.
16-97 Alarm Word 3
Range: Function:
0* [0 - 4294967295] View the alarm word 3 sent via the serial
communication port in hex code.
16-98 Warning Word 3
Range: Function:
0* [0 - 4294967295] View the warning word 3 sent via the
serial communication port in hex code.
3.13 Main Menu - Data Readouts 2 - Group
18
Parameters in this group are array parameters, where up to
10 fault logs can be viewed. [0] is the most recent logged
data, and [9] is the oldest. Fault codes, values, and time
stamp can be viewed for all logged data.
3.13.1 18-1* Fire Mode Log
18-10 FireMode Log:Event
Range: Function:
0* [0 - 255 ] View re mode event.
3.13.2 18-5* Ref. & Feedb.
18-50 Sensorless Readout [unit]
Range: Function:
0 Sensor-
lessUnit*
[-999999.999 -
999999.999
SensorlessUnit]
View the pressure or ow
resulting from the sensorless
calculations. This value is not the
value used for control. The value
is only updated if sensorless data
supports both ow and pressure.
Parameters
VLT
®
HVAC Basic Drive FC 101
84 Danfoss A/S © 04/2018 All rights reserved. MG18B502
33