Maintenance
3.4 Troubleshooting
Should problems occur, please check or correct the following before contacting your service representative. Always
check if there are any alarms active in the control panel.
1. Fan(s) do not start
Check if there are any alarm messages
Check that the fuses are not defect (figure 2)
Check the settings in the control panel (times, week schedule, auto/manual operation etc.)
2. Reduced airflow
Check the settings for medium and low fan speed
Check that the outdoor/exhaust air damper (if used) opens
Check if filters need changing
Check if diffusers and louvres need cleaning
Check diffuser/louvre openings
Check if fans and exchanger block need cleaning
Check if the roof unit or air intake is clogged
Check ducts for visible damage and/or build up of dust/pollution
3. Cold supply air
Check the control temperature on the control panel
Check if the overheating thermostat has tripped. If necessary press the red button, on the electrical heater (figure
2).
Check if the extract filter must be changed
Check if the fans have stopped due to overheating. If so the thermal contact might have tripped (shows as fan
alarm in the control panel).
4. Noise/vibrations
Check that the unit is completely levelled
Clean the fan impellers
Check that the screws holding the fans are tightened properly