Commissioning record Topvex (A011)

Function settings
|
11
Function
Default setting
Set value
Support control
No
Yes
No
Yes
Start heating room temperature 15 °C °
Stop heating room temperature
21 °C
°
Start cooling room temperature
30 °C
°
Stop cooling room temperature
28 °C
°
Preheater
No
Yes
No
Yes
Start/Stop function
Unit running
When defrosting
Unit running
When defrosting
Preheater setpoint:
-15 °C
°
Exchanger defrosting mode (only
applied for SC, SX/C, TX/C, FC units)
Pressure monitoring Pressure monitoring
Bypass On
Off
On
Off
Stop defrosting
On
Off
On
Off
Outdoor temp. to allow defrosting
18 °C
°
Outdoor temp. for stop of supply air fan
18 °C
°
Max deviation exchanger pressure to
start defrosting
50 %
%
Pressure hysteresis to end defrosting
60 %
%
Exchanger defrosting mode (only
applied units with section defrosting)
Section defrosting Section defrosting
Allow fan stop defrosting if exchanger
pressure > max limit
Yes
No
Yes
No
Max allowed deviation exchanger
pressure when defrosting
150%
%
Max deviation exchanger pressure to
start defrosting
25%
%
Pressure hysteresis to end defrosting
60%
%
Setpoint temperature min limit
4 °C
°
Temperature hysteresis to end
defrosting
4 °C
°
Calibration extract air flow
_____________
Calibration exchanger pressure
_____________