Commissioning record Topvex (A011)

34
| Alarm configuration
Alarm settings Def. settings
Set value
Alarm number 218
Alarm name Freeze protection alarm zone 3
Action
Fast stop
Level Class A
Delay
0 s
Alarm number 219
Alarm name Electric heater is overheated zone 1
Action
Normal stop
Level Class A
Delay
0 s
Alarm number 220
Alarm name Electric heater is overheated zone 2
Action
Normal stop
Level Class A
Delay
0 s
Alarm number 221
Alarm name Electric heater is overheated zone 3
Action
Normal stop
Level Class A
Delay
0 s
Alarm number 222
Alarm name Sensor error supply air temp zone 1
Action No action
Level Class B
Delay
5 s
206951 | A011