5.6.2 Condensation and heat insulation
Outdoor air duct and exhaust ducts must always be well insulated against condensation. Correct insulation installation
on ducts connected to the unit is especially important. All ducts installed in cold rooms/areas must be well insulated.
Use insulating covering (minimum 100 mm mineral wool) with plastic diffusion barrier. In areas with extremely low out-
door temperatures during the winter, additional insulation must be installed. Total insulation thickness must be at least
150 mm.
Caution
If the unit is installed in a cold place make sure that all joints are covered with insulation, and tape well
Duct connections/duct ends should be covered during storage and installation
Do not connect tumble dryers to the ventilation system
5.6.3 Silencers
To avoid fan noise being transferred via the duct system, silencers should be installed both on supply and extract air.
To avoid noise being transferred between rooms via the duct system and also to reduce noise from the duct system it-
self, installation of silencers before every inlet diffuser is recommended.
5.6.4 Electric connections
All electric connections are made in the electrical connection box which can be found on the long side of the unit (figure
10). The hatch is removed by unscrewing six screws as displayed in below figure (figure 10).
The unit must not be put into operation before all the electrical safety precautions have been read and understood. See
the enclosed wiring diagram for internal and external wiring.
All external connections to possible accessories are made to terminals inside the electrical connection box (chapter
5.6.6).
Fig. 10 Opening the electrical connection box
Danger
Make sure that the mains power supply to the unit is disconnected before performing any maintenance
or electrical work!
All electrical connections must be carried out by an authorized installer and in accordance with local rules
and regulations.
Warning
The units electrical connection to the mains power supply must be preceded by an all pole circuit breaker
with a minimum 3 mm gap.