Communication Manual

APPENDIX EXCEL TABLE PRINTOUT
Access version: 4.6-1-00 rev. 2
Signal name
EXOL
Type
Modbus type
Modbu
s
addres
RW
Bacnet
Scale
factor
Unit
Function Description Release
Access variable list
More information can be found in the Communication Manual
VentActual.A_AI_EAFPressure
R
Input Register (3x)
0300
R
AV, 40300
10
P
AI function
Actual value extract air pressure
VentActual.A_AI_SAFFlow
R
Input Register (3x)
0301
R
AV, 40301
Q
AI function
Actual value supply air flow
4.3-1-00
VentActual.A_AI_EAFFlow R Input Register (3x) 0302 R AV, 40302 1 Q AI function Actual value extract air flow 4.3-1-00
VentActual.A_ExchPressureSAF
R
Input Register (3x)
0303
R
AV, 40303
10
AI function
Actual value exchanger supply flow
VentActual.A_AI_ExchPressureEAF R Input Register (3x) 0304 R AV, 40304 10 AI function Actual value exchanger extract pressure
VentActual.A_AI_DeIcingTemp R Input Register (3x) 0305 R AV, 40305 10 AI function Actual value defrosting temperature
VentActual.A_AI_FrostprotTemp1(0)
R
Input Register (3x)
0306
R
AV, 40306
10
T
AI function
Actual value freeze protection temperature 1
VentActual.A_AI_FrostprotTemp2 R Input Register (3x) 0307 R AV, 40307 10 T AI function Actual value freeze protection temperature 2
VentActual.A_AI_FrostprotTemp3
R
Input Register (3x)
0308
R
AV, 40308
10
T
AI function
Actual value freeze protection temperature 3
VentActual.A_AI_CO2
R
Input Register (3x)
0309
R
AV, 40309
10
ppm
AI function
Actual value CO₂ room/extract air
VentActual.A_AI_HumidityRoom R Input Register (3x) 0310 R AV, 40310 10 % AI function Actual value humidity room/extract air
VentActual.A_AI_HumidityDuct
R
Input Register (3x)
0311
R
AV, 40311
10
%
AI function
Actual value humidity duct
VentActual.A_AI_HumidityOutDoor
R
Input Register (3x)
0312
R
AV, 40312
10
%
AI function
Actual value humidity outdoor
VentActual.A_AI_ExtraControllerTemp R Input Register (3x) 0313 R AV, 40313 10 AI function Actual value extra controller temperature
VentActual.A_AI_ExtSAFControl
R
Input Register (3x)
0314
R
AV, 40314
10
AI function
Actual value external control supply air fan
VentActual.A_AI_ExtEAFControl
R
Input Register (3x)
0315
R
AV, 40315
10
AI function
Actual value external control exract air fan
VentActual.A_AI_ExtraSensor1(0) R Input Register (3x) 0316 R AV, 40316 10 AI function Actual value extra sensor 1
VentActual.A_AI_ExtraSensor2
R
Input Register (3x)
0317
R
AV, 40317
10
AI function
Actual value extra sensor 2
VentActual.A_AI_ExtraSensor3 R Input Register (3x) 0318 R AV, 40318 10 AI function Actual value extra sensor 3
VentActual.A_AI_ExtraSensor4 R Input Register (3x) 0319 R AV, 40319 10 AI function Actual value extra sensor 4
VentActual.A_AI_ExtraSensor5
R
Input Register (3x)
0320
R
AV, 40320
10
AI function
Actual value extra sensor 5
VentActual.A_AI_ExternalSupplySetP R Input Register (3x) 0321 R AV, 40321 10 AI function Actual value external temperature setpoint
VentActual.A_AI_ExternalFlowSetP
R
Input Register (3x)
0322
R
AV, 40322
AI function
Actual value external supply air flow setpoint
4.3-1-00
VentActual.A_AI_FilterGuard1(0)
R
Input Register (3x)
0323
R
AV, 40323
10
AI function
Actual value supply air filter pressure
VentActual.A_AI_FilterGuard2 R Input Register (3x) 0324 R AV, 40324 10 AI function Actual value extract air filter pressure
VentActual.A_AI_EfficiencyTemp
R
Input Register (3x)
0325
R
AV, 40325
10
AI function
Actual value efficiency temperature
VentActual.A_AI_PreHeatTemp
R
Input Register (3x)
0326
R
AV, 40326
10
T
AI function
Actual value preheater temperature
4.3-1-00
VentActual.A_AI_Zone1SupplyTemp(0) R Input Register (3x) 0327 R AV, 40327 10 T AI function Actual value supply air temperature zone 1 4.3-1-00
VentActual.A_AI_Zone2SupplyTemp
R
Input Register (3x)
0328
R
AV, 40328
10
T
AI function
Actual value supply air temperature zone 2
4.3-1-00
VentActual.A_AI_Zone3SupplyTemp R Input Register (3x) 0329 R AV, 40329 10 T AI function Actual value supply air temperature zone 3 4.3-1-00
VentActual.A_AI_Zone1ExtractTemp(0) R Input Register (3x) 0330 R AV, 40330 10 T AI function Actual value extract air temperature zone 1 4.3-1-00
VentActual.A_AI_Zone2ExtractTemp
R
Input Register (3x)
0331
R
AV, 40331
10
T
AI function
Actual value extract air temperature zone 2
4.3-1-00
VentActual.A_AI_Zone3ExtractTemp R Input Register (3x) 0332 R AV, 40332 10 T AI function Actual value extract air temperature zone 3 4.3-1-00
VentActual.A_AI_Zone1RoomTemp(0)
R
Input Register (3x)
0333
R
AV, 40333
10
T
AI function
Actual value room temperature zone 1
4.3-1-00
VentActual.A_AI_Zone2RoomTemp
R
Input Register (3x)
0334
R
AV, 40334
10
T
AI function
Actual value room temperature zone 2
4.3-1-00
VentActual.A_AI_Zone3RoomTemp R Input Register (3x) 0335 R AV, 40335 10 T AI function Actual value room temperature zone 3 4.3-1-00
VentActual.A_RoomTemp
R
Input Register (3x)
0336
R
AV, 40336
10
T
AI function
Calculated average temperature of room sensor 1 to 4
VentInternal.I_ModbusReserved(0)
R
Input Register (3x)
0337
R
Spare
VentInternal.I_ModbusReserved(1) R Input Register (3x) 0338 R Spare
VentActual.A_AI_ExchAirFlowSAF
R
Input Register (3x)
0339
R
AV, 40339
Q
AI function
Calculated flow exchanger supply air
4.3-1-00
VentActual.A_ExchAirFlowEAF
R
Input Register (3x)
0340
R
AV, 40340
Q
AI function
Calculated flow exchanger extract air
4.3-1-00
VentActual.A_AO_SequenceY1 R Input Register (3x) 0341 R AV, 40341 10 % AO function Actual value SEQ-A
VentActual.A_AO_SequenceY2
R
Input Register (3x)
0342
R
AV, 40342
10
%
AO function
Actual value SEQ-B
VentActual.A_AO_SequenceY3 R Input Register (3x) 0343 R AV, 40343 10 % AO function Actual value SEQ-C
VentActual.A_AO_SequenceY4 R Input Register (3x) 0344 R AV, 40344 10 % AO function Actual value SEQ-D
VentActual.A_AO_SequenceY5
R
Input Register (3x)
0345
R
AV, 40345
10
%
AO function
Actual value SEQ-E
VentActual.A_AO_SequenceY6 R Input Register (3x) 0346 R AV, 40346 10 % AO function Actual value SEQ-F
VentActual.A_AO_SequenceY7
R
Input Register (3x)
0347
R
AV, 40347
10
%
AO function
Actual value SEQ-G
VentActual.A_AO_SequenceY8
R
Input Register (3x)
0348
R
AV, 40348
10
%
AO function
Actual value SEG-H
Page 7 of 45