Commissioning record Topvex (A011)

Function settings
|
5
Function
Default setting Set value
If DX cooler
Reduction of min limit supply air temp.
when DX cooling
5 °C °
Min setpoint deviation to allow start of
DX-cooling
2 °C
°
Control function cooling
0-10 V
Step controller
0-10 V
Step controller
If step controller
Type of step control Sequential
Binary
Sequential
Binary
Number of steps
1
2
3
4
1
2
3
4
Freeze protection
Type of freeze protection
None
Temp. sensor
Guard
None
Temp. sensor
Guard
Alarm limit when unit is running
7 °C
°
P-band when unit is running
5 °C
°
Set point when unit is stopped
20 °C
°
HW pump control
Pump running mode
Auto
Always running
Auto
Always running
Type of feedback
None
Alarm
Run indication
None
Alarm
Run indication
Pump stop delay
5 min
min
Pump running when outdoor temp. is
below:
10 °C
°
Hysteresis to allow pump stop
1 °C
°
206951 | A011