Commissioning
10 BKF 16.08.2021
WARNING
Connect the cable according to wiring diagram.
Tighten the nuts of cable glands well to achieve IP68 protection.
Place the supply cable.
7.1 Residual current circuit breaker
Use universal RCDs type B or B+ in case of speed control with frequency converter.
7.2 Connection of thermal protection
CAUTION
8 Commissioning
8.1 Preconditions
Mounting and electrical connection have been correctly performed.
Installation residuals and foreign objects have been removed from the fan and ducts.
Inlet and outlet are free.
The safety devices have been fitted (protection against contact with rotating impeller).
The protective conductor and external earth conductor have been connected.
The thermal protection is properly connected to the motor protective device:
- the motor protective device is functional;
- the thermal protection is functional.
The cable glands are tight (plug the not used cable glands).
Provided mains connection complies with the data on the nameplate.
The current (from the nameplate) does not exceed the mains data.