Modbus Parameter Specifications

Table Of Contents
MODBUS ACE V1.00
_______________________________________________________________________________________
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 ·74673 Mulfingen ·Phone: +49 (0) 7938/81-0 ·Fax: +49 (0) 7938/81-110 ·www.ebmpapst.com ·info1@de.ebmpapst.com
DocNo.: 634505DocNo: 446144DocNo.:358982DocNo.:322523DocNo.:309753DocNo.:303997DocNo.:276241DocNo.:256078DocNo.:196392 ·Template: 2 dated 10/6/2003 ·File: ext001931381.docx ·Last printed 9/30/2019 10:29:00
AM ·Page 27 of 78
Form 1003
MODBUS
address
Designation
Write
ebm-papst
Write
Customer
Write
End customer
Fact. setting
Address
Cust. setting
Address
D1A1
DC-link current reference value
X
-
-
-
-
D1A2
D1A3
Fan serial number
X
-
-
-
-
D1A4
Date of fan manufacture
X
-
-
-
-
D1A5 -
D1AA
Fan type
X
-
-
-
-
D1AB -
D1EC
Reserved
-
-
-
-
-
D1ED
Air flow reference value
X
-
-
-
-
D1EE
Mass flow reference value
X
-
-
-
-
D1EF -
D1FF
Reserved
-
-
-
-
-
D200 -
D27F
Customer settings
-
-
-
-
-
D280 -
D2FF
Factory settings
-
-
-
-
-
D300 -
D37F
Reserved
-
-
-
-
-
D380
D39F
Mirrored holding registers
See
original
See
original
See
original
-
-
D3A0 -
D3FF
Reserved
-
-
-
-
-
D400
D40F
Original addresses of mirrored input
registers
X
X
-
-
-
D410 -
D47F
Reserved
-
-
-
-
-
D480
D49F
Original addresses of mirrored holding
registers
X
X
-
-
-
D4A0 -
D601
Reserved
-
-
-
-
-
D602
Elevation above sea level
X
X
X
-
-
D603 -
D614
Reserved
-
-
-
-
-
*)
Only in part
There is no direct write access to the customer setting values (D200 - D27F) and the factory setting values
(D280 - D2FF). These holding registers can only be changed by way of the holding registers Customer Setting
Control and Factory Setting Control.
Coding of parameters:
Unless otherwise stated, parameters are coded in "big endian" format, i.e. the byte with the most
significant bits comes first. This applies in particular to parameters covering several holding registers.