2.39 Cable break detection voltage
Address : D15F
Write authorization : ebm-papst, customer
Only for Set value source (holding register D101) through analog input Ain1 (0)
If the voltage at the set value input Ain1 drops below the value defined here, the fan automatically switches to
the selected fail-safe set value source (holding register D15C). At the same time the direction of rotation is set
to the value "Rotating direction fail-safe mode" (see 2.35).
Coding:





Example:
Fail-safe mode function = on
Set value fail-safe speed = 100%
Input characteristic curve U_open circuit = 0.5 V
Input characteristic curve P1 = (0 V | 0%)
Input characteristic curve P2 = (10 V | 100%)
Motor stop enable = 1
This yields the following characteristic curve:
0.5 V
1 V
0%
0 V
P1
P2
10 V
100%
U [V]
Set value