Installation
The duct connected to the smoke damper must be supported or hung in such a way that the damper does not
carry its weight. The damper must not support any part of the surrounding construction or wall which could cause
damage and consequent damper failure.
The damper driving mechanism can be placed on either side of the wall, however, it needs to be situated to ensure
easy access during inspection.
According to the EN 1366-2 standard, the distance between the smoke damper bodies must be at least 200 mm.
According to the EN 1366-2 standard, the distance between smoke damper and the adjacent wall/ceiling
and the smoke damper must be at least 75 mm.
The S-SA2 smoke damper must be installed into a smoke and re partition structure in such a way that the damper
blade is located inside this structure in its closed position. To help you nd the suspension plane, a bendable hinge
is provided on the damper body. This condition does not apply for S-SA2L.
The gap in the installation opening between the smoke damper and the wall/ceiling can be increased by up to 50%
of the gap area, or decreased to the smallest amount possible that still provides sufcient space for the installation
of the seal.
The gap between the damper blade in the open position and the self-standing grill (when installed) must be at least
200 mm according to EN 1366-10. Otherwise, the damper must be tested together with the grill.
The smoke damper must be earthed after being installed into or onto the duct.
Lists of all permitted installation methods are provided on the following pages. Every method only applies to those
damper types that are listed in the corresponding paragraph’s heading.