IMO BKF

Electrical connection
BKF 16.08.2021 9
6.3 Installation
Ensure secure access to the fan for maintenance and service.
Installation up to Appendix 2.
Fit the contact surface between BKF and flexible connections/duct with temperature resistant sealing tape (not
provided with BKF).
WARNING
The fan shall be fixed with screws (hanging material not provided with BKF).
Ensure unobstructed and uniform intake into the fan as well as free outlet.
Install connecting ducts and accessories.
Provide for inlet/outlet contact/suction protection and safety distances according to EN ISO 13857.
7 Electrical connection
The wiring diagram is placed inside the cover of motor connection box (also in the test protocol). The quality and in-
stallation of cables for electrical connection must ensure uninterrupted energy supply, even in case of fire. Inside fire
zone use only certified cable. Connecting possibility see Appendix 3. Electrical data on the fan nameplate must comply
with the provided mains connection. Voltage tolerance according to IEC 38: +6%, -10%. Equivalent motors from differ-
ent suppliers may have slightly different nominal data than in catalogue.