DoP BKF

OSK 03-13-R0_I072AA_05_BKF_F400_DoP_09_08_2021.docx
Declaration of Perfomance
No.: I072AA.05-BKF-F400-DoP
1. Unique identification code of the product-type
BKF/F400
2. Type, batch or serial number or any other element allowing identification
of the construction product
BKF size/D motor pole(s)-impeller type/temperature-time
class
3. Intended use of the construction product
Powered smoke and heat exhaust ventilator for use in
construction works
4. Name and contact address of the manufacturer
Systemair d.o.o. Špelina ulica 2, 2000 Maribor, Slovenia
5. System of assessment and verification of constancy of performance of
the construction product
System 1
6. In case of the declaration of performance concerning a construction
product covered by a harmonized standard
EN 12101-3:2015
Name and identification number of the notified bodies
BSI Group The Netherlands B.V., id. number: 2797
Description of tasks, performed by the notified bodies
Determination of the product type on the basis of type
testing (including sampling), type calculation, tabulated
values or descriptive documentation of the product;
initial inspection of the manufacturing plant and of factory
production control;
continuous surveillance, assessment and evaluation of
factory production control.
EC Certificate of conformity, issued by the notified bodies
2797-CPR-597958
Essential
characteristics
Performance/Reference
Harmonized
technical
specification
Temperature/
time
classification
F400
a)
Test reports No. P 1015/15-530-1, No. P 1297/15-
530-1, Range report No. P 1297/15-530-2, issued by
the ZAG, Ljubljana, Slovenia;
EC Certificate 2797-CPR-597958
a)
minimum functioning period at tests 120 min
EN 12101-3:2015,
Smoke and heat
control systems-
Part 3: Specification
for powered smoke
and heat control
ventilators
Wind load
NPD
Snow load
NPD
Application
classes
For use outside building, motor weather
protected, any position of motor shaft
Range report No. P 1297/15-530-2, issued by the
ZAG, Ljubljana, Slovenia;
EC Certificate 2797-CPR-597958
For use inside building, outside fire zone
in well ventilated room, motor pointing
downwards or horizontal drive shaft
position
Dual purpose
Tested
accessories
Flexible connection FLC BKF
Weather protection WPR BKF
Steel spring vibration isolator
Frequency converter without sine filter
(tested with BKF)
S
igned for and on behalf of the manufacturer by:
Maribor, 09.08.2021 Anton Zupančič, Director
2797-CPR-597958

Summary of content (1 pages)