DeclarationOfPerformance F B90 Bsigned
3/3 | F-B90
Assessment of F-B90
Property Test regulation Classification
standard
Technical
specification for
assessment
Performance
expressed
Evaluation
Nominal activation
/Sensing element
conditions
/sensitivity
ISO 10294-4 / EN 15650
4.2.1.2
4.2.1.2.2
4.2.1.2.3
• load-bearing
capacity
in accordance with
ISO 10294-4, 4.2;
• response
temperature
in accordance with
ISO 10294-4, 4.2;
Satisfied
Response delay
(response time)
EN 1366-2 / EN 15650
4.2.1.3
• closure time
within time period
of 2 minutes
Satisfied
Operational
reliability
EN 1366-2
cl. 10.2
/ EN 15650
4.3.1 a)
50 cycles Satisfied
Fire resistance
• integrity
• insulation
• smoke leakage
• mechanical
stability
EN 1366-2 EN 13501-3 + A1 EN 15650,
cl. 4.1.1, a),
cl. 4.1.1 b),
cl. 4.1.1 c),
cl. 4.1.1 a),
See installation
Table 9.
Satisfied
Fire resistance
• maintenance of
cross-section
EN 1366-2 EN 13501-3 + A1 EN 15650,
cl. 4.4.1 a)
See installation
Table 9.
Satisfied
Durability of
response delay
ISO 10294-4 / EN 15650
4.3.3.1
Durability of
response delay
(by tested
temperature
response and load-
bearing capacity)
is preserved.
Satisfied
Durability of
operational
reliability
EN 15650
Annex C
/ EN 15650
4.3.3.2
10 000 cycles
for actuator
mechanism
20 000 cycles
for MOD actuator
mechanism
50 cycles - for
manual
mechanism
Satisfied
This declaration of performance is issued under the sole responsibility of the manufacturer identified in point 4.
Signed for and on behalf of the manufacturer by:
Kalinkovo, August 24, 2021 Ing. Maroš Chlebo, Managing Director