OPTIMA-S-FM Air Flow Measurement Device Handbook
/15 | OPTIMA-S-FM Table of Contents Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Dimensions & Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Ordering Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
/15 | OPTIMA-S-FM Description The air flow measurement device OPTIMA-S...FM is intended for continuous reading of the air flow volume in the rectangular-shaped ventilation ducts. The air flow volume is interpreted and transmited by the analog signal or by the bus communication. Highlights • Precise continuous air flow volume reading • Measurement data transfer via analog signal, or Bus line: Modbus or BACnet • Compact dimensions • No maintenance Design OPTIMA-S...
/15 | OPTIMA-S-FM Product Parts OPTIMA-S-FM-...-BM OPTIMA-S-FM-...
/15 | OPTIMA-S-FM Dimensions & Weights (mm) OPTIMA-S-FM-...-BM H H+40 114 W 250 W+40 (mm) OPTIMA-S-FM-...
/15 | OPTIMA-S-FM OPTIMA-S-FM-...
/15 | OPTIMA-S-FM Ordering Codes Nominal dimension WxH W: 200 mm ... 1200 mm (50 mm step) H: 100 mm ... 1000 mm (50 mm step) OEM, Communication type SA Siemens, Analog BM Belimo, Analog, Modbus, BACnet Example of the Ordering Code OPTIMA-S-FM-400x200-BM Air flow measurement device with rectangular shape of nominal dimension 400x200, analog, modbus or BACnet communication, OEM Belimo.
/15 | OPTIMA-S-FM Installation OPTIMA-S-FM-...
/15 | OPTIMA-S-FM Measurement The air flow transmitter measures the flow velocity dependent dynamic pressure on the measurement probe. For both OEM/Communication types, BM and SA the air flow volume is interpreted by the transmitter in the form of analog signal U in the 0 V ... 10 V or the 2 V ... 10 V mode from the analog output. The air flow volume q can be calculated using this analog voltage value and the nominal air flow volume Vnom of the measurement device.
/15 | OPTIMA-S-FM W H mm 100 200 250 300 350 400 450 Vnom @ 11 m/s m /h 3 W H mm 792 100 Vnom @ 11 m/s m /h 3 W H (mm) 1980 150 Vnom @ 11 m/s (m /h) 3 W H (mm) Vnom @ 11 m/s (m3/h) 3861 200 6336 7920 150 1188 150 2970 200 5148 250 200 1584 200 3960 250 6435 300 9504 100 990 250 4950 300 7722 350 11088 150 1485 300 5940 350 9009 400 12672 200 1980 350 6930 400 10296 450 14256 250 2475 400 7920 450 11583 500 15840 100 1188 450 8910
/15 | OPTIMA-S-FM W H (mm) 200 900 950 Vnom @ 11 m/s (m /h) 3 W H (mm) Vnom @ 11 m/s (m /h) 3 W H (mm) Vnom @ 11 m/s (m /h) 3 W H (mm) Vnom @ 11 m/s (m3/h) 7128 300 11880 300 13068 400 19008 250 8910 350 13860 350 15246 450 21384 300 10692 400 15840 400 17424 500 23760 350 12474 450 17820 450 19602 550 26136 400 14256 500 19800 500 21780 600 28512 450 16038 550 21780 550 23958 650 30888 500 17820 600 23760 600 26136 1200 700 33264 55
/15 | OPTIMA-S-FM Electrical Connections Type of Measurement Transmitter BM Supply voltage: DC/AC 24V Terminals: 2,5 mm² Power rating: 2 VA Type of Measurement Transmitter SA Supply voltage: AC 24V Cable (6 wires): 0,75 mm² Power rating: 1 VA Legend G wire 1-1 red phase AC 24 V G0 wire 2-1 black common conductor U wire 9-1 pink flow measurement signal DC 0 V ...
/15 | OPTIMA-S-FM Transport, Storage and Operation
/15 | OPTIMA-S-FM Supplement Any deviations from the technical specifications contained herein and the terms should be discussed with the manufacturer. We reserve the right to make any changes to the product without prior notice, provided that these changes do not affect the quality of the product and the required parameters. Current information on all products is available on design.systemair.com.
Systemair DESIGN • 2022-01-26 • Handbook_OPTIMA_S_FM_en-GB • F90C87A7-CA83-48B2-9750-CD587F33E823 • Original instructions