Variable Air Volume Controllers | 15 / 24
RC-C3DOC
Room Controller
For VAV air ow control based on multiple physical values and control states in different congurable operation modes
and sequences.
Functions
The room controller has the following main control functions:
• Heating control, separate controls of the heating valve and VAV in heating mode
• Cooling control, separate controls of the cooling valve and VAV in cooling mode
• CO
2
(or VOC, or humidity or other values) control by VAV
• Dew point surveillance protection
• Frost protection
• Different operation modes switched according to room occupation state
• Energy conservation procedures in case of room control conditions disturbance (e.g. open window)
The following measurement and detection capabilities are included or can be connected to the RC:
• Room temperature measurement on board
• External temperature measurement connectable via analog input
• External CO
2
(or other value) measurement connectable via analog input
• External change-over switch connectable via digital input
• External dew point detection connectable via digital input
• External presence/occupation detection connectable via digital input
• External window opening detection connectable via digital input