DataSheet OPTIM201910 en GB
Table Of Contents
2 / 24 | Variable Air Volume Controllers
Controls
The residential VAV system is equipped with BLC4 type compact controllers in the master/slave connection.
The controllers use analog input for the setpoint signal and analog output for the feedback signal. The type of the
signals is DC 0 V ... 10 V. The VAV controllers are factory calibrated as standard to the air volume indicated in the table
below or, upon request, they can be adjusted to site required settings of the V
min
/V
max
range. The air volumes can
also be readjusted on site with the ZTH-EU
hand held service tool. If specic air volumes for V
min
and V
max
would be
required, they must be indicated in the ordering code or noted in the order for adequate calibration in the factory.
Factory Settings
Size V
min
@ 2 m/s V
max
@ 9 m/s V
nom
@ 11 m/s
(mm) (m
3
/h) (l/s) (m
3
/h) (l/s) (m
3
/h) (l/s)
100 57 16 254 71 311 86
125 88 24 398 111 486 135
160 145 40 651 181 796 221
Basic Functional Characteristics
Controller type: OPTIMA-RES-A-…BLC4
Basic Parameters and Features
Flow volume adjustment setpoint signal:
Analog input DC 0 V … 10 V. The Systemair MZ3-Touch room control device is primarily foreseen to be connected
to the analog input. It can operate in automatic mode, continuously controlling the air ow volume dependent from
temperature, VOC or CO
2
concentration. If switched to manual mode, the air ow setpoint can be adjusted manually in
four discrete steps between the preset V
min
and V
max
of OPTIMA-RES-A.
Other control devices with 0 V ... 10 V control output can also be used, e.g. Systemair RC-C3DOC.
Controller parameters setup tools: Belimo ZTH-EU
Feedback signal (actual air ow volume): Analog output DC 0 V … 10 V
Power supply (each VAV controller, secured by transformer on board):
AC 24 V/50 Hz DC 24 V
4 VA 2 W
Power supply (whole system): AC 230 V/50 Hz
Protection class (closed system box): IP40
Master/Slave Conguration
The VAV system is congured as master/slave. The supply air VAV controller (the master) reads the ow volume
setpoint from an external source like e.g. a room controller or manual setpoint dial. The control range (V
min
, V
max
) of
the master VAV controller can be adjusted at the factory or on site with the ZTH-EU conguration tool. The feedback
signal from master VAV represents the actual measured air ow volume. This signal is connected to the extract air
VAV controller (the slave) as the setpoint for the air ow volume. So the air ow volumes of supply and extract air are
always equal with high reliability.