InstalMaintenOperInstr PP 100 01 TSP

Diffusers
|
Installation instruction
TSP
Installation instruction
K-factor size
Air gap
10 mm 20 mm 30 mm
TSP-100 6,2 9,4 12,1
TSP-125 8,0 12,4 15,8
TSP-160 10,4 16,6 23,0
TSP-200 11,9 18,9 26,1
TSP-250 16,0 26,9 38,8
K-factor
Example
Formula given
q = k · √ Pi
Where: q = airow (l/s)
k = K-factor
P
i
= adjustment pressure (Pa)
Adjustment
Use the cord to adjust the damper until the required
airow is reached acc. to formula.
Using the formula to calculate airow
Size: TSP-160
Gap: 30 mm
K-factor (from label): 23,0
Measured pressure: 10 Pa
Entered in the equation:
q = 23,0 · √10 = 72,7 l/s
Systemair AB, Industrivägen 3, 739 30 Skinnskatteberg, Sweden
Tel +46 222 440 00 Fax +44 222 440 99 mailbox@systemair.se
PP-100-01 Systemair 09 / 2013
Cleaning
The diffusers normally requires no cleaning, but may be
cleaned with lukewarm water and a mild detergent.
Dismounting
Loosen the damper by loosening the two domed nuts
on the outside of the connection.