UserManual TSR201309

Diffusers
|
Installation instruction
TSR
Installation instruction
K-factor size
Air gap
10 mm 20 mm 30 mm 40 mm
TSR-100 5,6 7,5 8,8 8,8
TSR-125 7,1 9,6 11,7 13,4
TSR-160 8,1 11,4 14,9 17,5
TSR-200 12,2 18,2 23,2 28,3
TSR-250 13,4 19,6 26,4 32,2
K-factor
Example
Formula given
q = k · √ Pi
Where: q = airow (l/s)
k = K-factor
P
i
= adjustment pressure (Pa)
Adjustment
Use the cord to adjust the damper until the required
airow is reached acc. to formula.
Using the formula to calculate airow
Si ze: TS R-16 0
Gap: 30 mm
K-factor (from label): 14,9
Measured pressure: 10 Pa
Entered in the equation:
q = 14,9 · √10 = 47 l/s
Systemair AB, Industrivägen 3, 739 30 Skinnskatteberg, Sweden
Tel +46 222 440 00 Fax +44 222 440 99 mailbox@systemair.se
PP-100-02 Systemair 09 / 2013
Cleaning
The diffusers normally requires no cleaning, but may be
cleaned with lukewarm water and a mild detergent.
Dismounting
Loosen the damper by loosening the two domed nuts
on the outside of the connection.