Installation |
19
Installation positions
AXC-EX, AXCBF-EX
The installation is possible in the mounting positions, see
adjacent picture.
AW-EX
Important
Damage to the fan if condensation water can not drain.
If installed in a vertical motor shaft position, condensation cannot escape.
Install the fan in a horizontal shaft position.
8.2 Installation RVK-EX
Air gap
Table 13 Air gap RVK-EX
Nominal diameter Min. air gap [mm]
315 2
Important
The electrical connection of the fan must be performed on site. Observe the max. tightening torque of 2.3
Nm of the fan`s cable gland.
Installation positions
The installation is possible in any mounting position.
Installation with mounting bracket
Note:
The mounting
bracket is
included with the
delivery.
Mount the mounting
bracket on the fan,
see adjacent image.